Interval 2
P3.11.2.1: ON Time: 09:00:00
P3.11.2.2: OFF Time: 13:00:00
P3.11.2.3: From Day: Saturday
P3.11.2.4: To Day: Sunday
P3.11.2.5: Assign to channel: Time channel 1
Timer 1
You can start the motor with the digital input 1 on slot A during other times than those
specified with the intervals. In this case, the timer specifies the duration that the motor runs.
P3.11.6.1: Duration: 1800 s (30 min)
P3.11.6.2: Assign to channel: Time channel 1
P3.5.1.18: Timer 1: DigIn SlotA.1 (The parameter located in the digital inputs menu)
Interval 1
ON = 07:00:00 hrs OFF = 17:00:00 hrs
Interval 2
From = Saturday
To = Sunday
From = Monday
To = Friday
ON = 09:00:00 hrs OFF = 13:00:00 hrs
P Ctrl Signal 1A
Digital input 1
on Slot A
Timer 1
Duration = 1800 s
Time channel 1
Start/Stop
Fig. 36: Time channel 1 is used as the control signal for the start command instead of a digital
input
P3.11.1.1 ON TIME (ID 1464)
Use this parameter to set the time of day when the output of the interval function is activated.
P3.11.1.2 OFF TIME (ID 1465)
Use this parameter to set the time of day when the output of the interval function is
deactivated.
P3.11.1.3 FROM DAY (ID 1466)
Use this parameter to set the day when the output of the interval function is activated.
P3.11.1.4 TO DAY (ID 1467)
Use this parameter to set the day when the output of the interval function is deactivated.
P3.11.1.5 ASSIGN TO CHANNEL (ID 1468)
Use this parameter to select the time channel where the output of the interval function is
assigned.
You can use the time channels to control the on/off type functions, for example relay outputs
or any functions that can be controlled by a DI signal.
PARAMETER DESCRIPTIONS
VACON · 165