Starting order of motors
ID428 =FALSE
M1
M2
M3
M4
M5
Fig. 46: The interlock logic 2
If you add Motor 3 again (you set the value of P3.5.1.36 to CLOSED), the system puts Motor 3
last in the sequence: 1, 2, 4, 5, 3. The system does not stop, but continues to operate.
New starting order of motors
ID428 = TRUE
M1
M2
M4
M5
M3
Fig. 47: The interlock logic 3
When the system stops or goes to sleep mode for the next time, the sequence changes back
to 1, 2, 3, 4, 5.
P3.14.3 INCLUDE FC (ID 1028)
Use this parameter to include the controlled motor/pump in the autochange and interlock
system.
PARAMETER DESCRIPTIONS