Table 10: Motor control settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.2.1
Switching Frequency
1.5
Varies
kHz
Varies
601
P3.1.2.2
Motor Switch
0
1
0
653
0 = Disabled
1 = Enabled
P3.1.2.4
Zero Frequency Volt-
age
0.00
40.00
%
Varies
606
P3.1.2.5
Motor preheat func-
tion
0
3
0
1225
0 = Not used
1 = Always in stop state
2 = Controlled by DI
3 = Temp limit (heat-
sink)
P3.1.2.6
Motor preheat tem-
perature limit
-20
100
°C
0
1226
P3.1.2.7
Motor preheat cur-
rent
0
0.5*I
L
A
Varies
1227
P3.1.2.8
U/f Ratio selection
0
1
Varies
108
0=Linear
1=Squared
P3.1.2.15
Overvoltage Control
0
1
1
607
0 = Disabled
1 = Enabled
P3.1.2.16 Undervoltage Control
0
1
1
608
0 = Disabled
1 = Enabled
P3.1.2.17 Stator Voltage Adjust
50.0
150.0
%
100.0
659
P3.1.2.18
Energy Optimization
0
1
0
666
0 = Disabled
1 = Enabled
P3.1.2.19
Flying Start Options
0
65
1590
B0 = Disable reverse
direction search
B6 = Flux build with
current control
P3.1.2.20
I/f Start
0
1
0
534
0 = Disabled
1 = Enabled
P3.1.2.21
I/f Start Frequency
5.0
25
Hz
0.2 *
P3.1.1.2
535
P3.1.2.22
I/f Start Current
0
100
%
80
536