Table 12: Control reference settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.11
Preset Frequency 0
P3.3.1
P3.3.2
Hz
5.00
180
P3.3.12
Preset Frequency 1
P3.3.1
P3.3.1
Hz
10.00
105
P3.3.13
Preset Frequency 2
P3.3.1
P3.3.1
Hz
15.00
106
P3.3.14
Preset Frequency 3
P3.3.1
P3.3.1
Hz
20.00
126
P3.3.15
Preset Frequency 4
P3.3.1
P3.3.1
Hz
25.00
127
P3.3.16
Preset Frequency 5
P3.3.1
P3.3.1
Hz
30.00
128
P3.3.17
Preset Frequency 6
P3.3.1
P3.3.1
Hz
40.00
129
P3.3.18
Preset Frequency 7
P3.3.1
P3.3.1
Hz
50.00
130
P3.3.19
Preset alarm fre-
quency
P3.3.1
P3.3.2
Hz
25.00
183
P3.3.20
Motor Potentiometer
Ramp Time
0.1
500.0
Hz/s
10.0
331
P3.3.21
Motor Potentiometer
Reset
0
2
1
367
0 = No reset
1 = Reset if stopped
2 = Reset if powered
down
P3.3.22
Reverse direction
0
1
0
15530 0 = Reverse allowed
1 = Reverse prevented
PARAMETERS MENU
VACON · 59
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]