2
Go into the Parameter backup submenu.
STOP
READY
Keypad
ID:
M6.5
User settings
Language selection
English
Parameter backup
( 7 )
Drive name
Drive
3
Use the arrow buttons Up and Down to make a
selection of a function. Accept the selection with
the OK button.
STOP
READY
Keypad
ID:
M6.5.1
Parameter backup
Restore factory defaults
Save to keypad
Restore from keypad
The command Restore factory defaults brings back the parameter settings that were made
at the factory. With the command Save to keypad you can copy all the parameters to the
control panel. The command Restore from keypad copies all the parameters from the
control panel to the drive.
The parameters that you cannot copy if the drives have a different size
If you replace the control panel of a drive with a control panel from a drive that is of a
different size, the values of these parameters do not change.
•
Motor nominal voltage (P3.1.1.1)
•
Motor nominal frequency (P3.1.1.2)
•
Motor nominal speed (P3.1.1.3)
•
Motor nominal current (P3.1.1.4)
•
Motor cos phii (P3.1.1.5)
•
Motor nominal power (P3.1.1.6)
•
Motor current limit (P3.1.1.7)
•
Switching frequency (P3.1.2.1)
•
Zero frequency voltage (P3.1.2.4)
•
Motor preheat current (P3.1.2.7)
•
Stator voltage adjust (P3.1.2.17)
•
Maximum frequency (P3.3.2)
•
Start magnetizing current (P3.4.8)
•
DC brake current (P3.4.10)
•
Flux braking current (P3.4.13)
•
Stall current limit (P3.9.5)
•
Motor thermal time constant (P3.9.9)
VACON · 34
USER INTERFACES
3
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205