5.15
GROUP 3.16: FIRE MODE
Table 43: Fire mode parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.16.1
Fire Mode Password
0
9999
0
1599
1002 = Enabled
1234 = Test mode
P3.16.2
Fire Mode Activ.
Open
DigIN
Slot0.2
1596
Open = Fire Mode
active
closed = No action
P3.16.3
Fire Mode Activ.
Close
DigIN
Slot0.1
1619
Open = No action
Closed = Fire Mode
active
P3.16.4
Fire Mode Frequency
8.00
P3.3.2
Hz
50.00
1598
P3.16.5
Fire Mode Frequency
Source
0
8
0
1617
0 = Fire Mode fre-
quency
1 = Preset speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor potentiome-
ter
P3.16.6
Fire Mode Reverse
DigIN
Slot0.1
1618
Open = Forward
Closed = Reverse
P3.16.7
Fire Mode preset fre-
quency 1
0
50
10
15535
P3.16.8
Fire Mode preset fre-
quency 2
0
50
Hz
20
15536
P3.16.9
Fire Mode preset fre-
quency 3
0
50
30
15537
M3.16.10
Fire Mode Status
0
3
0
1597
A 0 = Disabled
1 = Enabled
2 = Activated (Enabled
+ DI Open)
3 = Test Mode
M3.16.11
Fire Mode Counter
0
1679
P3.16.12
Fire Mode Run Indi-
cation Current
0.0
100.0
%
10.0
15580
PARAMETERS MENU
VACON · 87