Goodrive10 inverters Communication protocol
91
Code
Name
Meaning
01H
Illegal command
The command from master can not be executed. The reason maybe:
1. This command is only for new version and this version can not realize.
2. Slave is in fault state and can not execute it.
02H
Illegal data
address.
Some of the operation addresses are invalid or not allowed to access.
Especially the combination of the register and the transmitting bytes are
invalid.
03H
Illegal value
When there are invalid data in the message framed received by slave.
Note:
This error code does not indicate the data value to write exceed
the range, but indicate the message frame is an illegal frame.
04H
Operation failed
The parameter setting in parameter writing is invalid. For example, the
function input terminal can not be set repeatedly.
05H
Password error
The password written to the password check address is not same as the
password set by P7.00.
06H
Data frame error
In the frame message sent by the upper monitor, the length of the digital
frame is incorrect or the counting of CRC check bit in RTU is different
from the lower monitor.
07H
Written not
allowed.
It only happen in write command, the reason maybe:
1. The written data exceeds the parameter range.
2. The parameter should not be modified now.
3. The terminal has already been used.
08H
The parameter
can not be
changed during
running
The modified parameter in the writing of the upper monitor can not be
modified during running.
09H
Password
protection
When the upper monitor is writing or reading and the user password is
set without password unlocking, it will report that the system is locked.
The slave uses functional code fields and fault addresses to indicate it is a normal response or some error
occurs (named as objection response). For normal responses, the slave shows corresponding function
codes, digital address or sub-function codes as the response. For objection responses, the slave returns a
code which equals the normal code, but the first byte is logic 1.
For example: when the master sends a message to the slave, requiring it to read a group of address data of
the inverter function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it will return:
1 0 0 0 0 0 1 1 (Hex 83H)
Besides the function codes modification for the objection fault, the slave will respond a byte of abnormal