Goodrive10 inverters Function codes
31
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.18
Function
restore
parameter
0:No operation
1:Restore the default value
2:Clear fault records
Note:
The function code will restore to 0 after finishing the
operation of the selected function code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0
◎
P01 Group Start-up and stop control
P01.00
Start mode
0:Start-up directly:start from the starting frequency P01.01
1:Start-up after DC braking: start the motor from the starting
frequency after DC braking (set the parameter P01.03 and
P01.04). It is suitable in the cases where reverse rotation
may occur to the low inertia load during starting.
0
◎
P01.01
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the original
frequency during the inverter starting. See P01.02 for
detailed information.
Setting range: 0.00~50.00Hz
0.50Hz
◎
P01.02
Retention time
of the starting
frequency
Set a proper starting frequency to increase the torque of the
inverter during starting. During the retention time of the
starting frequency, the output frequency of the inverter is
the starting frequency. And then, the inverter will run from
the starting frequency to the set frequency. If the set
frequency is lower than the starting frequency, the inverter
will stop running and keep in the stand-by state. The
starting frequency is not limited in the lower limit frequency.
Setting range: 0.0~50.0s
0.0s
◎
P01.03
The braking The inverter will carry out DC braking at the braking current
0.0%
◎