Goodrive10 inverters Function codes
64
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.05
Current limit
action
selection
The actual increasing ratio is less than the ratio of output
frequency because of the big load during ACC running. It is
necessary to take measures to avoid overcurrent fault and
the inverter trips.
During the running of the inverter, this function will detect
the output current and compare it with the limit level defined
in P11.06. If it exceeds the level, the inverter will run at
stable frequency in ACC running, or the inverter will derate
to run during the constant running. If it exceeds the level
continuously, the output frequency will keep on decreasing
to the lower limit. If the output current is detected to be
lower than the limit level, the inverter will accelerate to run.
Setting range of P11.05:
0:current limit invalid
1:current limit valid
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
1
◎
P11.06
Automatic
current limit
level
160.0%
◎
P11.07
The
decreasing
ratio during
current limit
10.00Hz/s
◎
P11.08
Overload
pre-alarm of
the motor or
the inverter
The output current of the inverter or the motor is above
P11.09 and the lasting time is beyond P11.10, overload
pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the inverter or
0x000
○
P11.09
Overload
pre-alarm test
level
150%
○
P11.10
Overload
pre-alarm
detection time
1.0s
○