Goodrive10 inverters Function codes
60
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P09.08
PID control
deviation limit
As shown in the diagram below, PID adjustor stops to work
during the deviation limit. Set the function properly to adjust
the accuracy and stability of the system.
Setting range:0.0~100.0%
0.0%
○
P09.09
Output upper
limit of PID
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. Frequency
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
100.0%
○
P09.10
Output lower
limit of PID
0.0%
○
P09.11
Feedback
offline
detection
value
Set the PID feedback offline detection value, when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report “PID feedback
offline fault” and the keypad will display PIDE
.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0.0%
○
P09.12
Feedback
offline
detection time
1.0s
○
P09.13
PID
adjustment
0x00~0x11
LED ones:
0x00
○