Goodrive10 inverters Function codes
67
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
delay
the drive receive the data and sent it to the upper monitor. If
the answer delay is shorter than the system processing
time, then the answer delay time is the system processing
time, if the answer delay is longer than the system
processing time, then after the system deal with the data,
waits until achieving the answer delay time to send the data
to the upper monitor.
P14.04
Communicatio
n overtime
fault time
0.0(invalid),0.1~60.0s
When the function code is set as 0.0, the communication
overtime parameter is invalid.
When the function code is set as non-zero, if the interval
time
between
two
communications
exceeds
the
communication overtime, the system will report “485
communication faults” (CE).
Generally, set it as invalid; set the parameter in the
continuous communication to monitor the communication
state.
0.0s
○
P14.05
Transmission
fault
processing
0:Alarm and stop freely
1:No alarm and continue to run
2:No alarm and stop according to the stop means(only
under the communication control)
3:No alarm and stop according to the stop means(under all
control modes)
0
○
P14.06
Communicatio
n processing
action
selection
0x00~0x11
LED ones:
0: Operation with response: the drive will respond to all
reading and writing commands of the upper monitor.
1: Operation without response
;
The drive only responds to
the reading command other than the writing command of
the drive. The communication efficiency can be increased
by this method.
LED tens:(reserved)
0x00
○
P17 Group Monitoring function
P17.00
Set frequency
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
0.00Hz
●