Goodrive10 inverters Function codes
40
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.04
S4 terminals
function
selection
11:Decreasing frequency setting(DOWN)
12:Cancel the frequency change setting
13:Shift between A setting and B setting
14:Shift between combination setting and A setting
15:Shift between combination setting and B setting
16:Multi-stage speed terminal 1
17:Multi-stage speed terminal 2
18:Multi-stage speed terminal 3
19:Multi- stage speed terminal 4
20:Multi- stage speed pause
21:ACC/DEC time option 1
25:PID control pause
26:Traverse Pause (stop at the current frequency)
27:Traverse reset (return to the center frequency)
28:Counter reset
30:ACC/DEC prohibition
31:Counter trigger
33:Cancel the frequency change setting temporarily
34:DC brake
36:Shift the command to the keypad
37:Shift the command to the terminals
38:Shift the command to the communication
0
◎
P05.05
S5 terminals
function
selection
0
◎
P05.10
Polarity
selection of
the input
terminals
The function code is used to set the polarity of the input
terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
The setting range:0x000~0x1F
0x000
○
P05.11
Switch filter
time
Set the sample filter time of S1~S5 and HDI terminals. If the
interference is strong, increase the parameter to avoid the
disoperation.
0.000~1.000s
0.010s
○
P05.12
Virtual
terminals
setting
Enable the input function of virtual terminals at the
communication mode.
0:Virtual terminals is invalid
0
◎