Goodrive10 inverters Function codes
38
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The setting range of P04.01:0.0%:(automatic)0.1%~10.0%
The setting range of P04.02:0.0%~50.0%
P04.03
Motor V/F
frequency
point 1
When P04.00 =1, the user can set V//F curve through
P04.03~P04.08.
V/F is generally set according to the load of the motor.
Note:V1
<
V2
<
V3,f1
<
f2
<
f3. Too high low frequency
voltage will heat the motor excessively or damage. The
inverter may occur the overcurrent speed or overcurrent
protection.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04, P04.06 and P04.08 :
0.0%~110.0%
The setting range of P04.05: P04.03~ P04.07
The setting range of P04.07:P04.05~P02.02(the rated
frequency of motor 1)
0.00Hz
○
P04.04
Motor V/F
voltage
point 1
00.0%
○
P04.05
Motor V/F
frequency
point 2
00.00Hz
○
P04.06
Motor V/F
voltage point 2
00.0%
○
P04.07
Motor V/F
frequency
point 3
00.00Hz
○
P04.08
Motor V/F
voltage point 3
00.0%
○
P04.09
Motor V/F slip
compensation
gain
This function code is used to compensate the change of the
rotation speed caused by load during compensation
SVPWM control to improve the rigidity of the motor. It can
be set to the rated slip frequency of the motor which is
counted as below:
△
f=f
b
-n*p/60
380V:
100.0%
○