Goodrive10 inverters Function codes
44
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
10:Upper limit frequency arrival
11:Lower limit frequency arrival
12:Ready for operation
14:Overload pre-alarm
15:Underload pre-alarm
16:Achievement of simple PLC stage
17:Achievement of simple PLC cycle
18:Setting count value arrival
19:Defined count value arrival
20:External fault valid
22:Running time arrival
23:MODBUS communication virtual terminals output
P06.05
Polarity of
output
terminals
The function code is used to set the pole of the output
terminal.
When the current bit is set to 0, input terminal is positive.
When the current bit is set to 1, input terminal is negative.
BIT3
BIT2
BIT1
BIT0
Reserved
RO1
Reserved
Y
Setting range:00~0F
00
○
P06.06
Y1 switching
on delay time
0.000~50.000s
0.000s
○
P06.07
Y1 switching
off delay time
0.000~50.000s
0.000s
○
P06.10
RO switching
on delay time
The function code defines the corresponding delay time of
the electrical level change during the programmable
terminal switching on and off.
The setting range :0.000~50.000s
0.000s
○
P06.11
RO switching
off delay time
0.000s
○
P06.14
AO output
0:Running frequency
1:Set frequency
2:Ramp reference frequency
0
○