Goodrive10 inverters Function codes
37
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
the overload coefficient =116%, the fault will be reported
after 1 hour, when the overload coefficient=200%, the fault
will be reported after 1 minute.
Setting range: 20.0%~120.0%
P04 Group SVPWM control
P04.00
Motor V/F
curve setting
These function codes define the V/F curve of Goodrive10
motor to meet the need of different loads.
0:Straight line V/F curve
;
applying to the constant torque
load
1:Multi-dots V/F curve
0
◎
P04.01
Torque boost Torque boost to the output voltage for the features of low
frequency torque. P04.01 is for the Max. Output voltage V
b
.
P04.02 defines the percentage of closing frequency of
manual torque to f
b
.
Torque boost should be selected according to the load. The
bigger the load is, the bigger the torque is. Too big torque
boost is inappropriate because the motor will run with over
magnetic, and the current of the inverter will increase to add
the temperature of the inverter and decrease the efficiency.
When the torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost threshold: below this frequency point, the
torque boost is valid, but over this frequency point, the
torque boost is invalid.
0.0%
○
P04.02
Torque boost
close
20.0%
○