Goodrive10 inverters Installation guidelines
17
Terminal
sign
Terminal name
Function
Grounding terminal
Each machine has a standard PE terminal.
Note:
Do not use an asymmetrically constructed motor cable. If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the conductive shield, connect the grounding conductor to the
grounding terminal at the inverter and motor ends.
Route the motor cable, input power cable and control cables separately.
“T”
terminal can not be wired in single-phase input.
3.2.3 Wiring of terminals in main circuit
1. Fasten the grounding conductor of the input power cable with the grounding terminal of the inverter (
PE
)
by
360
degree grounding technique. Connect the phase conductors to
R/L1, S/L2, T/L3
and
T
terminals and
fasten.
2. Strip the motor cable and connect the shield to the grounding terminal of the inverter by
360
degree
grounding technique. Connect the phase conductors to
U
,
V
and
W
terminals and fasten.
3. Connect the optional brake resistor with a shielded cable to the designated position by the same
procedures in the previous step.
4. Secure the cables outside the inverter mechanically.
3.2.4 Connection diagram of the control circuit
Figure 3-5 Connection diagram of the control circuit