Goodrive10 inverters Installation guidelines
14
Environment
Conditions
Humidity
RH
≤
90%
No condensation is allowed.
The maximum relative humility should be equal to or less than 60% in
corrosive air.
Storage
temperature
-40
℃
~
+
70
℃
, and the temperature changing rate is less than 1
℃
/minute.
Running environment
condition
The installation site of the inverter should:
keep away from the electromagnetic radiation source;
keep away from contaminative air, such as corrosive gas, oil mist and
flammable gas;
ensure foreign objects, such as metal power, dust, oil, water can not enter
into the inverter(do not install the inverter on the flammable materials such as
wood);
keep away from direct sunlight, oil mist, steam and vibration environment.
Altitude
Below 1000m
If is installed above 1000m of the sea level derate 1% for every additional
100m.
Vibration
≤
5.8m/s
2
(0.6g)
Installation direction
The inverter should be installed on an upright position to ensure sufficient
cooling effect.
Note:
Goodrive10 series inverters should be installed in a clean and ventilated environment according
to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The inverter may be installed on the wall or in a cabinet.
The inverter must be installed in an upright position. Check the installation site according to the requirements
below. Refer to chapter
Dimension Drawings
in the appendix for frame details.