Goodrive10 inverters Function codes
45
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3:Running rotation speed
4:Output current (relative to 2 times of the rated current of
the inverter)
5:Output current(relative to 2 times of the rated current of
the motor)
6:Output voltage
7:Output power
8:Set torque value
9:Output torque
10:Analog AI1 input value
11:Analog AI2 input value
14:MODBUS communication set value 1
15:MODBUS communication set value 2
P06.17
Lower limit of
AO output
The above function codes define the relative relationship
between the output value and analog output. When the
output value exceeds the range of set maximum or
minimum output, it will count according to the low-limit or
upper-limit output.
When the analog output is current output, 1mA equals to
0.5V.
In different cases, the corresponding analog output of
100% of the output value is different. Please refer to each
application for detailed information.
10V (20mA)
0.0%
100.0%
AO
Setting range of P06.18 0.00V~10.00V
Setting range of P06.19 P06.17~100.0%
Setting range of P06.20 0.00V~10.00V
Setting range of P06.21 0.000s~10.000s
0.0%
○
P06.18
Corresponding
AO output to
the lower limit
0.00V
○
P06.19
Upper limit of
AO output
100.0%
○
P06.20
The
corresponding
AO output to
the upper limit
10.00V
○
P06.21
AO output filter
time
0.000s
○
P07 Group Human-Machine Interface
P07.00
User’s
0~65535
0
○