33
• 1 = SPT RESET
Space temperature will be used as the reset control variable
along with both
RTIO
and
LIMT
in the calculation of the
final amount of reset to be applied (
Inputs
RSET
SA.S.R
).
• 2 = RAT RESET
Return-air temperature will be used as the reset control vari-
able along with both
RTIO
and
LIMT
in the calculation of
the final amount of reset to be applied (
Inputs
RSET
SA.S.R
).
• 3 = 3RD PARTY RESET
The reset value is determined by a 4 to 20 mA third party
input. An input of 4 mA would correspond to 0º F reset. An
input of 20 mA would correspond to 20º F reset. Configur-
ing the control for this option will cause
RES.S
to become
enabled automatically with the CEM board. To avoid
alarms make sure the CEM board and third party input are
connected first before enabling this option.
Reset Ratio (
RTIO
) — This configuration is used when
RS.CF
is set to 1 or 2. For every degree that the controlling
temperature (space/return) falls below the occupied cooling
setpoint (
OCSP
), the calculated value of the supply air reset
will rise by the number of degrees as specified by this
parameter.
Reset Limit (
LIMT
) — This configuration is used when
RS.CF
is set to 1 or 2. This configuration places a clamp on the
amount of supply air reset that can be applied.
EDT 4-20 mA Reset Input (
RES.S
) — This configuration is
automatically enabled when
Configuration
EDT.R
RS.CF
is set to 3 (third party reset).
COOLING CONFIGURATION — Relevant configurations for
mechanical cooling are located at the local display under
Configuration
COOL
.
See Table 36.
Capacity Threshold Adjust (
Z.GN
) — This configuration is
used for units using the “SumZ” algorithm for cooling capacity
control (
Configuration
UNIT
C.TYP
= 1, 2, 3 or 5). The
configuration affects the cycling rate of the cooling stages by
raising or lowering the threshold that demand must rise above
in order to add or subtract a stage of cooling.
Normally this configuration should not require any tuning or
adjustment. If there is an application where the unit may be sig-
nificantly oversized and there are indications of high compres-
sor cycles, then the Capacity Threshold Adjust (
Z.GN
) can be
used to adjust the overall logic gain. Normally this is set to 1.0,
but it can be adjusted from 0.5 to 4.0. As the value of
Z.GN
is
increased, the cycling of cooling stages will be slowed.
Table 34 — Setpoints
Table 35 — Supply Air Reset Configuration
Table 36 — Cooling Configuration
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40-99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40-99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40-99
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2-10
^F
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0-25
^F
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1-25
^F
VAVOCOFF
2
SASP
Supply Air Setpoint
45-75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
90-145
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
–20-80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
–20-80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
–20-80
dF
TEMPVUNC
50
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
EDT.R
EVAP.DISCHRGE TEMP RESET
RS.CF
EDT Reset Configuration
0 - 3
EDRSTCFG
0
RTIO
Reset Ratio
0 - 10
RTIO
2
LIMT
Reset Limit
0 - 20
^F
LIMT
10
RES.S
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
COOL
COOLING CONFIGURATION
Z.GN
Capacity Threshold Adjst
–10 - 10
Z_GAIN
1
MC.LO
Compressor Lockout Temp
–20 - 55
dF
OATLCOMP
40
C.FOD
Fan-Off Delay, Mech Cool
0-600
sec
COOL_FOD
60
MLV
Min. Load Valve (HGBP)?
Yes/No
MLV_SEL
No
M.M.
Motor Master Control ?
Yes/No
MOTRMAST
No
MM.OF
Motor Master Setpoint Offset
–20 - 20
dF
MMSPOFST
–10
MM.RR
Motor Master PD Run Rate
10-120
sec
MM_RATE
10
MM.PG
Motor Master Proportional Gain
0.0-5
MM_PG
1
MM.DG
Motor Master Derivative Gain
0-5
MM_DG
0.3
MM.TI
Motor Master Integration Time
0-50
MM_TI
30
DS.EN
Enable Digital Scroll?
Yes/No
DIGCMPEN
No
DS.MC
DS Min Digital Capacity
25 - 100
%
MINCAPDS
50
DS.AP
Dig Scroll Adjust Delta
0 - 100
%
DSADJPCT
100
DS.AD
Dig Scroll Adjust Delay
15 - 60
sec
DSADJDLY
20
DS.RP
Dig Scroll Reduce Delta
0 - 100
%
DSREDPCT
6
DS.RD
Dig Scroll Reduce Delay
15 - 60
sec
DSREDDLY
30
DS.RO
Dig Scroll Reduction OAT
70 - 120
dF
DSREDOAT
95
DS.MO
Dig Scroll Max Only OAT
70 - 120
dF
DSMAXOAT
105
HPSP
Head Pressure Setpoint
80 - 150
dF
HPSP
110
A1.EN
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
A2.EN
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
B1.EN
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
B2.EN
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
CS.A1
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
CS.A2
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
CS.B1
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
CS.B2
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
REV.R
Rev. Rotation Verified?
Yes/No
REVR_VER
No
H.SST
Hi SST Alert Delay Time
5 - 30
min
HSSTTIME
10
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...