CONTROLS SETPOINT AND CONFIGURATION LOG
MODEL NUMBER:
Software Version
SERIAL NUMBER:
MBB
CESR131343--
DATE:
RCB
CESR131249--
TECHNICIAN:
ECB
CESR131465-
NAVI
CESR131227--
SCB
CESR131226--
CEM
CESR131174--
MARQ
CESR131171--
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 - 6 (multi-text strings)
4
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 - 1 (multi-text strings)
1
RM.CF
Remote Switch Config
0 - 3 (multi-text strings)
0
CEM
CEM Module Installed
Yes/No
No
TCS.C
Temp.Cmp.Strt.Cool Factr
0 - 60 min
0
TCS.H
Temp.Cmp.Strt.Heat Factr
0 - 60 min
0
SFS.S
Fan Fail Shuts Down Unit
Yes/No
No
SFS.M
Fan Stat Monitoring Type
0 - 2 (multi-text strings)
0
VAV.S
VAV Unocc.Fan Retry Time
0 - 720 min
50
SIZE
Unit Size (20-60)
20 - 60
20
DP.XR
Disch.Press. Transducers
Yes/No
No
SP.XR
Suct. Pres. Trans. Type
0 -1 (multi-text strings)
0
RFG.T
Refrig: 0=R22 1=R410A
0 -1 (multi-text strings)
1
CND.T
Cnd HX Typ:0=RTPF 1=MCHX
0 -1 (multi-text strings)
0
MAT.S
MAT Calc Config
0 - 2 (multi-text strings)
1
MAT.R
Reset MAT Table Entries?
Yes/No
No
MAT.D
MAT Outside Air Default
0-100%
20
ALTI
Altitude……..in feet:
0 - 60000
0
DLAY
Startup Delay Time
0 - 900 sec
0
STAT
TSTAT_Both Heat and Cool
Yes/No
No
AUX.R
Auxiliary Relay Config
0 - 3
0
SENS
INPUT SENSOR CONFIG
SPT.S
Space Temp Sensor
Enable/Disable
Disable
SP.O.S
Space Temp Offset Sensor
Enable/Disable
Disable
SP.O.R
Space Temp Offset Range
1 - 10
5
RRH.S
Return Air RH Sensor
Enable/Disable
Disable
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
Disable
COOL
COOLING CONFIGURATION
Z.GN
Capacity Threshold Adjst
–10 - 10
1
MC.LO
Compressor Lockout Temp
–20 to 55 dF
40
C.FOD
Fan-off Delay, Mech Cool
0 - 600 sec
60
MLV
Min. Load Valve? (HGBP)
Yes/No
No
M.M.
Motor Master Control?
Yes/No
No
MM.OF
Motor Master Setpoint Offset
–20 - 20
–10
MM.RR
Motor Master PD Run Rate
10 - 120
10
MM.PG
Motor Master Proportional Gain
0.0 - 5
1
MM.DG
Motor Master Derivative Gain
0 - 5
0.3
MM.TI
Motor Master Integration Time
0 - 50
30
DS.EN
Enable Digital Scroll?
Yes/No
No
DS.MC
DS Min Digital Capacity
25 - 100%
50
DS.AP
Dig Scroll Adjust Delta
0 - 100%
100
DS.AD
Dig Scroll Adjust Delay
15 - 60 sec
20
DS.RP
Dig Scroll Reduce Delta
0 - 100%
6
DS.RD
Dig Scroll Reduce Delay
15 - 60 sec
30
DS.RO
Dig Scroll Reduction OAT
70 - 120 dF
95
DS.MO
Dig Scroll Max Only OAT
70 - 120 dF
105
HPSP
Head Pressure Setpoint
80 - 150 dF
110
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...