![United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 185](http://html1.mh-extra.com/html/united-technologies/carrier-weathermaker-48a2/carrier-weathermaker-48a2_controls-start-up-operation-service-and-troubleshooting_4065174185.webp)
185
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
See legend on page 189.
POINT DESCRIPTION
CCN
POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Econ Recovery Hold Off?
ECONHELD
R
n/a
n/a
n/a
BV:42
econheld_1
Econo Current Min. Pos.
MIN_POS
R
%
n/a
n/a
AV:66
min_pos_1
Econo Position Override
ECOORIDE
W
n/a
n/a
0-1
BV:41
ecooride_1
Economizer Act. Cmd. Pos.
ECONOCMD
W
%
n/a
0-100
AV:67
econocmd_1
Economizer Act. Curr. Pos
ECONOPOS
R
%
n/a
n/a
AV:1028
econ_pos_1
Economizer Active?
ECACTIVE
R
n/a
n/a
n/a
BV:36
ecactive_1
Economizer Control Input
ECOSW
W
n/a
n/a
0-1
BV:37
ecosw_1
Economizer Control Point
ECONCPNT
R
°F
n/a
n/a
AV:68
econpnt_1
Economizer Forced ?
ECONFORC
R
n/a
n/a
n/a
BV:38
econforc_1
Economizer Max.Position
ECONOMAX
W
%
98
0-100
AV:70
economax_1
Economizer Min.Position
ECONOMIN
W
%
5
0-100
AV:4005
econ_min_1
EDT Sensor Bad ?
EDT_STAT
R
n/a
n/a
n/a
BV:44
edt_stat_1
Element Comm Status
n/a
n/a
n/a
n/a
n/a
BV:2999
element_stat_1
Emergency Stop
EMSTOP
W
n/a
n/a
0-1
BV:45
emstop_1
Enable Compressor A1
CMPA1ENA
W
n/a
Enable
0-1
BV:46
cmpa1ena_1
Enable Compressor A2
CMPA2ENA
W
n/a
Enable
0-1
BV:47
cmpa2ena_1
Enable Compressor B1
CMPB1ENA
W
n/a
Enable
0-1
BV:48
cmpb1ena_1
Enable Compressor B2
CMPB2ENA
W
n/a
Enable
0-1
BV:49
cmpb2ena_1
Evacuation Input
EVAC
W
n/a
n/a
0-1
BV:1060
smk_evac_1
Evaporator Discharge Tmp
EDT
R
°F
n/a
n/a
AV:76
edt_1
Exhaust Fan VFD Speed
EFAN_VFD
R
%
n/a
n/a
AV:2075
ef_vfd_output_1
Fan Fail Shuts Down Unit
SFS_SHUT
W
n/a
0
0-1
BV:50
sfs_shut_1
Fan Mode
FAN_MODE
W
n/a
1
0-1
AV:77
fan_mode_1
Fan request from IGC
IGCFAN
R
n/a
n/a
n/a
BV:11
igcfan_1
Fan-Off Delay, Elec Heat
ELEC_FOD
W
n/a
30
10-600
AV:78
elec_fod_1
Fan-Off Delay, Gas Heat
GAS_FOD
W
n/a
45
45-600
AV:79
gas_fod_1
Fan-Off Delay, Mech Cool
COOL_FOD
W
sec
60
0-600
AV:80
cool_fod_1
Filter Status Input
FLTS
W
n/a
n/a
0-1
BV:1052
filter_status_1
Fire Shutdown Input
FSD
W
n/a
n/a
0-1
BV:1005
firedown_status_1
Heat Interlock Relay
HIR
W
n/a
n/a
0-1
BV:1026
heat_interlock_relay_1
Heat Relay 1
HS1
R
n/a
n/a
n/a
BV:52
hs1_1
Heat Relay 2
HS2
R
n/a
n/a
n/a
BV:53
hs2_1
Heat-Cool Setpoint Gap
HCSP_GAP
W
°^F
5
10-Feb
AV:83
hcsp_gap_1
Heating Control Point
HEATCPNT
R
°F
n/a
n/a
AV:1025
heat_ctrl_point_1
Heating Occupied Setpoint
OHSP
W
°F
68
409-99
AV:3002
occ_ht_stpt_1
Heating Supply Air Setpt
SASPHEAT
W
°F
85
80-120
AV:85
saspheat_1
Heating Unoccupied Setpoint
UHSP
W
°F
55
40-99
AV:3004
unocc_ht_stpt_1
Hi Limit Switch Tmp Mode
LIMTMODE
R
n/a
n/a
n/a
BV:55
limtmode_1
High BP Level
BPHPLVL
W
n/a
0.05
0-1
AV:86
bphplvl_1
High BP Override
BPHPOVRD
R
n/a
n/a
n/a
BV:54
bphpovrd_1
High OAT Lockout Temp
OAT_LOCK
W
°F
60
-160
AV:9008
econ_oat_lockout_1
HumidiMiZer 3-way Valve
HUM3WVAL
R
0-1
BV:47
Hum3wval_1
HumidiMiZer Capacity
HMZRCAPC
R
%
0-100
AV:57
Hmzrcapc_1
HVAC Mode Numerical Form
MODEHVAC
R
n/a
n/a
n/a
AV:1022
hvac_mode_1
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...