62
The following information can be found under the Local
Display Mode
Run Status
ECON
.
See Table 65.
Economizer Control Point Determination Logic — Once the
economizer is allowed to provide free cooling, the economizer
must determine exactly what setpoint it should try to maintain.
The setpoint the economizer attempts to maintain when “free
cooling” is located at
Run Status
VIEW
EC.C.P
. This is
the economizer control point.
The control selects setpoints differently, based on the con-
trol type of the unit. This control type can be found at
Configuration
UNIT
C.TYP
. There are 6 types of control.
C.TYP
= 1
VAV-RAT
C.TYP
= 2
VAV-SPT
C.TYP
= 3
TSTAT Multi-Staging
C.TYP
= 4
TSTAT 2 Stage
C.TYP
= 5
SPT Multi-Staging
C.TYP
= 6
SPT 2 Stage
If the economizer is not allowed to do free cooling, then
EC.C.P
= 0.
If the economizer is allowed to do free cooling and the
Unoccupied Free Cooling Mode is ON, then
EC.C.P
=
Setpoints
SASP
+
Inputs
RSET
SA.S.R
.
If the economizer is allowed to do free cooling and the
Dehumidification mode is ON, then
EC.C.P
= the Cooling
Control Point (
Run Status
VIEW
CL.C.P
).
If the
C.TYP
is either 4 or 6, and the unit is in a cool mode,
then
If Stage = 0
EC.C.P
= the Cooling Control Point (
Run
Status
VIEW
CL.C.P
)
If Stage = 1
53.0 + economizer suction pressure reset (see
below)
If Stage = 2
48.0 + economizer suction pressure reset (see
below)
NOTE: To check the current cooling stage go to
Run Status
Cool
CUR.S
.
If the
C.TYP
is either 1,2,3 or 5, and the unit is in a cool
mode, then
EC.C.P
= the Cooling Control Point (
Run Status
VIEW
CL.C.P
).
Economizer Suction Pressure Reset for Two-Stage
Cooling — If the unit’s control type is set to either 2-stage ther-
mostat or 2-stage space temperature control, then there is no
cooling control point. Stages 1 and 2 are brought on based on
demand, irrespective of the evaporator discharge temperature.
In this case, the economizer monitors suction pressure and
resets the economizer control point accordingly in order to
protect the unit from freezing. For those conditions when the
economizer opens up fully but is not able to make setpoint, and
then a compressor comes on, it is conceivable that the coil
might freeze. This can be indirectly monitored by checking suc-
tion pressure. Rather than fail a circuit, the control will attempt
to protect the unit by resetting the economizer control point
until the suction pressure rises out of freezing conditions.
If either circuit’s suction pressure drops to within 5 psig
of the low suction pressure trip point, the control will start
adding reset to the economizer control point if it is active. It
will be possible to reset the control point upwards, 10 degrees
(2 degrees per psig), between the low suction pressure trip
point of 93 psig. If this does not work, and if the suction pres-
sure drops below the trip point, then the control will further re-
set the control point 1 degree every 15 seconds up to a maxi-
mum of 10 degrees. The resulting effect will be to warm up the
mixed air entering the evaporator, thereby raising the suction
pressure.
Building Pressure Control —
The building pressure
control sequence provides control of the pressure in the build-
ing through the modulating flow rate function of the modulat-
ing power exhaust option. This function also provides control
of the constant volume 2-stage power exhaust option.
BUILDING PRESSURE CONFIGURATION — The build-
ing pressure configurations are found at the local display under
Configuration
BP
.
See Table 66.
Building Pressure Config (
BP.CF
) — This configuration se-
lects the type of building pressure control.
•
BP.CF
= 0, No building pressure control
•
BP.CF
= 1, constant volume two-stage power exhaust
based on economizer position
•
BP.CF
= 2, multiple stage building pressure control
based on a building pressure sensor
•
BP.CF
= 3, VFD building pressure control based on a
building pressure sensor
Building Pressure PID Run Rate (
BP.RT
) — This configura-
tion selects the run time of the PID algorithm. This configura-
tion is only active when
BP.CF
= 3. It is recommended that this
value not be changed without guidance from Service
Engineering.
Building Pressure Proportional Gain (
BP.P
) — This configura-
tion selects the proportional gain of the PID algorithm. This
configuration is only active when
BP.CF
= 3. It is recommend-
ed that this value not be changed without guidance from Service
Engineering.
Table 65 — Economizer Run Status Table
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
ACTV
Economizer Active ?
YES/NO
ECACTIVE
DISA
ECON DISABLING CONDITIONS
UNAV
Econ Act. Unavailable?
YES/NO
ECONUNAV
R.EC.D
Remote Econ. Disabled?
YES/NO
ECONDISA
DBC
DBC - OAT Lockout?
YES/NO
DBC_STAT
DEW
DEW - OA Dewpt.Lockout?
YES/NO
DEW_STAT
DDBC
DDBD- OAT > RAT Lockout?
YES/NO
DDBCSTAT
OAEC
OAEC- OA Enth Lockout?
YES/NO
OAECSTAT
DEC
DEC - Diff.Enth.Lockout?
YES/NO
DEC_STAT
EDT
EDT Sensor Bad?
YES/NO
EDT_STAT
OAT
OAT Sensor Bad ?
YES/NO
OAT_STAT
FORC
Economizer Forced ?
YES/NO
ECONFORC
SFON
Supply Fan Not On 30s ?
YES/NO
SFONSTAT
CLOF
Cool Mode Not In Effect?
YES/NO
COOL_OFF
OAQL
OAQ Lockout in Effect ?
YES/NO
OAQLOCKD
HELD
Econ Recovery Hold Off?
YES/NO
ECONHELD
DH.DS
Dehumid. Disabled Econ.?
YES/NO
DHDISABL
O.AIR
OUTSIDE AIR INFORMATION
OAT
Outside Air Temperature
dF
OAT
forcible
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
OA.E
Outside Air Enthalpy
OAE
OA.D.T
Outside Air Dewpoint Temp
dF
OADEWTMP
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...