166
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
STAGEGAS
Heating Mode………..:
Requested Heat Stage
HT_STAGE
Heating Control Point
HEATCPNT
Staged Gas LAT Sum
dF
LAT_SGAS
Staged Gas LAT 1
dF
LAT1SGAS
Staged Gas LAT 2
dF
LAT2SGAS
Staged Gas LAT 3
dF
LAT3SGAS
Staged Gas Limit Sw.Temp
dF
LIMSWTMP
Heat PID Timer
sec
HTSGTIMR
Staged Gas Capacity Calc
%
HTSGCALC
Current Running Capacity
%
HTSG_CAP
Proportional Cap. Change
HTSG_P
Derivative Cap. Change
HTSG_D
Maximum Heat Stages
HTMAXSTG
Hi Limit Switch Tmp Mode
LIMTMODE
LAT Cutoff Mode
LATCMODE
Capacity Clamp Mode
CAPMODE
STRTHOUR
Compressor A1 Run Hours
hours
HR_A1
config
Compressor A2 Run Hours
hours
HR_A2
config
Compressor B1 Run Hours
hours
HR_B1
config
Compressor B2 Run Hours
hours
HR_B2
config
Compressor A1 Starts
CY_A1
config
Compressor A2 Starts
CY_A2
config
Compressor B1 Starts
CY_B1
config
Compressor B2 Starts
CY_B2
config
SUMZ
Cooling Control Point
dF
COOLCPNT
Mixed Air Temperature
dF
MAT
Evaporator Discharge Tmp
dF
EDT
Return Air Temperature
dF
RAT
Outside Air Temperature
dF
OAT
Econo Damper Current Pos
%
ECONOPOS
Capacity Threshold Adjst
Z_GAIN
Capacity Load Factor
SMZ
Next Stage EDT Decrease
ADDRISE
Next Stage EDT Increase
SUBRISE
Rise Per Percent Capacity
RISE_PCT
Cap Deadband Subtracting
Y_MINUS
Cap Deadband Adding
Y_PLUS
Cap Threshold Subtracting
Z_MINUS
Cap Threshold Adding
Z_PLUS
High Temp Cap Override
On/Off
HI_TEMP
Low Temp Cap Override
On/Off
LOW_TEMP
Pull Down Cap Override
On/Off
PULLDOWN
Slow Change Cap Override
On/Off
SLO_CHNG
SYSTEM
Reset All Current Alarms
Yes/No
ALRESET
config
Reset the Device
Yes/No
RESETDEV
config
Local Machine Disable
Yes/No
UNITSTOP
config
Soft Stop Request
Yes/No
SOFTSTOP
forcible
Emergency Stop
Enable/Disable
EMSTOP
forcible
CEM AN1 10K temp J5,1-2
-40 - 240
dF
CEM10K1
forcible
CEM AN2 10K temp J5,3-4
-40 - 240
dF
CEM10K2
forcible
CEM AN3 10K temp J5,5-6
-40 - 240
dF
CEM10K3
forcible
CEM AN4 10K temp J5,7-8
-40 - 240
dF
CEM10K4
forcible
CEM AN1 4-20 ma J5,1-2
0-20
ma
CEM4201
forcible
CEM AN2 4-20 ma J5,3-4
0-20
ma
CEM4202
forcible
CEM AN3 4-20 ma J5,5-6
0-20
ma
CEM4203
forcible
CEM AN4 4-20 ma J5,7-8
0-20
ma
CEM4204
forcible
TESTCOOL
Compressor A1 Relay
ON/OFF
CMPA1TST
test
Compressor A2 Relay
ON/OFF
CMPA2TST
test
Min. Load Valve (HGBP)
ON/OFF
MLV_TST
test
Compressor B1 Relay
ON/OFF
CMPB1TST
test
Compressor B2 Relay
ON/OFF
CMPB2TST
test
Digital Scroll Capacity
0-100
%
DSCAPTST
test
Humidimizer 3-Way Valve
ON/OFF
RHVC_TST
test
Condenser EXV Position
0-100
%
CEXVCTST
test
Bypass EXV Position
0-100
%
BEXVCTST
test
TESTFANS
Supply Fan Relay
ON/OFF
SFAN_TST
test
Supply Fan VFD Speed
0.0-100
%
SFVFDTST
test
Exhaust Fan VFD Speed
0.0-100
%
EFVFDTST
test
MtrMaster A Commanded %
0.0-100
%
OAVFDTST
test
MtrMaster B Commanded %
0.0-100
%
OBVFDTST
test
Condenser Fan Circuit A
ON/OFF
CNDA_TST
test
Condenser Fan Circuit B
ON/OFF
CNDB_TST
test
MotorMastr Fan Circuit A
ON/OFF
MM_A_TST
test
MotorMastr Fan Circuit B
ON/OFF
MM_B_TST
test
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...