APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
See legend on page 189.
POINT DESCRIPTION
CCN
POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Supply Fan Request
SFANFORC
W
n/a
n/a
0-1
BV:2004
sfan_forc_1
Supply Fan State
SFAN
R
n/a
n/a
n/a
BV:2001
sfan_1
Supply Fan Status Switch
SFS
W
n/a
n/a
0-1
BV:95
sfs_1
Supply Fan VFD Speed
SFVFDTST
W
%
n/a
0-100
AV:165
sf_vfd_output_1
Supply Fan VFD Speed
SFAN_VFD
R
%
n/a
n/a
AV:2050
sfvfdtst_1
Temp Comp Start Cool Factor
TCSTCOOL
W
min
0
0-60
AV:159
tcstcool_1
Temp Comp Start Heat Factor
TCSTHEAT
W
min
0
0-60
AV:160
tcstheat_1
Temp Compensated Start
MODETCST
R
n/a
n/a
n/a
BV:96
modetcst_1
Temper Supply Air Setpt
SASPTEMP
W
°F
n/a
0-100
AV:15
sasptemp_1
Temper Vent Unocc
TEMPVUNC
W
n/a
50
-100
AV:164
tempvunc_1
Tempering in Cool SASP
TEMPCOOL
W
n/a
5
May-75
AV:161
tempcool_1
Tempering Purge SASP
TEMPPURG
W
n/a
50
-100
AV:162
temppurg_1
Tempering Vent Occ SASP
TEMPVOCC
W
n/a
65
-100
AV:163
tempvocc_1
Thermostat G Input
G
W
n/a
n/a
0-1
BV:1021
g_input_1
Thermostat W1 Input
W1
W
n/a
n/a
0-1
BV:1019
w1_input_1
Thermostat W2 Input
W2
W
n/a
n/a
0-1
BV:1020
w2_input_1
Thermostat Y1 Input
Y1
W
n/a
n/a
0-1
BV:1017
y1_input_1
Thermostat Y2 Input
Y2
W
n/a
n/a
0-1
BV:1018
y2_input_1
Timed Override In Effect
MODETOVR
R
n/a
n/a
n/a
BV:97
modetovr_1
Timed-Override in Effect
OVERLAST
R
n/a
n/a
n/a
BV:98
overlast_1
TSTAT Both Heat and Cool
TSTATALL
W
n/a
No
0-1
BV:99
tstatall_1
Un.Ec.Free Cool OAT Lock
UEFCNTLO
W
°F
50
40-70
AV:166
uefcntlo_1
Unoc Econ Free Cool Cfg
UEFC_CFG
W
n/a
0
0-2
AV:172
uefc_cfg_1
Unoc Econ Free Cool Time
UEFCTIME
W
min
120
0-720
AV:173
uefctime_1
Unoccupied Cool Mode End
UCCL_END
R
°F
n/a
n/a
AV:168
uccl_end_1
Unoccupied Cool Mode Start
UCCLSTRT
R
°F
n/a
n/a
AV:169
ucclstrt_1
Unoccupied Heat Mode End
UCHT_END
R
°F
n/a
n/a
AV:170
ucht_end_1
Unoccupied Heat Mode Start
UCHTSTRT
R
°F
n/a
n/a
AV:171
uchtstrt_1
User Defined Analog 1
n/a
n/a
n/a
n/a
n/a
AV:2901
user_analog_1_1
User Defined Analog 2
n/a
n/a
n/a
n/a
n/a
AV:2902
user_analog_2_1
User Defined Analog 3
n/a
n/a
n/a
n/a
n/a
AV:2903
user_analog_3_1
User Defined Analog 4
n/a
n/a
n/a
n/a
n/a
AV:2904
user_analog_4_1
User Defined Analog 5
n/a
n/a
n/a
n/a
n/a
AV:2905
user_analog_5_1
User Defined Binary 1
n/a
n/a
n/a
n/a
n/a
BV:2911
user_binary_1_1
User Defined Binary 2
n/a
n/a
n/a
n/a
n/a
BV:2912
user_binary_2_1
User Defined Binary 3
n/a
n/a
n/a
n/a
n/a
BV:2913
user_binary_3_1
User Defined Binary 4
n/a
n/a
n/a
n/a
n/a
BV:2914
user_binary_4_1
User Defined Binary 5
n/a
n/a
n/a
n/a
n/a
BV:2915
user_binary_5_1
User Determined OAQ
OAQ_USER
W
n/a
400
0-5000
AV:179
oaq_user_1
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...