![United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 146](http://html1.mh-extra.com/html/united-technologies/carrier-weathermaker-48a2/carrier-weathermaker-48a2_controls-start-up-operation-service-and-troubleshooting_4065174146.webp)
146
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS
*The display text changes depending on the remote switch configuration (
Configuration
UNIT
RM.CF
). If
RM.CF
is set to 0 (No Remote
Switch), then the display text will be “On” or “Off.” If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If
RM.CF
is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
GEN.I
GENERAL INPUTS
FLT.S
Filter Status Input
DRTY/CLN
FLTS
forcible
G.FAN
Fan Request From IGC
ON/OFF
IGCFAN
REMT
Remote Input State
*
RMTIN
forcible
E.SW
Economizer Control Input
YES/NO
ECOSW
forcible
E.ENA
Remote Economizer Enable
YES/NO
ECONENBL
forcible
E.OVR
Econo Position Override
YES/NO
ECOORIDE
forcible
S.FN.S
Supply Fan Status Switch
ON/OFF
SFS
forcible
DL.S1
Demand Limit Switch 1
ON/OFF
DMD_SW1
forcible
DL.S2
Demand Limit Switch 2
ON/OFF
DMD_SW2
forcible
DH.IN
Dehumidify Switch Input
ON/OFF
DHDISCIN
forcible
FD.BK
COMPRESSOR FEEDBACK
CS.A1
Compressor A1 Feedback
ON/OFF
CSB_A1
CS.A2
Compressor A2 Feedback
ON/OFF
CSB_A2
CS.B1
Compressor B1 Feedback
ON/OFF
CSB_B1
CS.B2
Compressor B2 Feedback
ON/OFF
CSB_B2
STAT
THERMOSTAT INPUTS
G
Thermostat G Input
ON/OFF
G
forcible
W1
Thermostat W1 Input
ON/OFF
W1
forcible
W2
Thermostat W2 Input
ON/OFF
W2
forcible
Y1
Thermostat Y1 Input
ON/OFF
Y1
forcible
Y2
Thermostat Y2 Input
ON/OFF
Y2
forcible
FIRE
FIRE-SMOKE INPUTS
FSD
Fire Shutdown Input
ALARM/NORMAL
FSD
forcible
PRES
Pressurization Input
ALARM/NORMAL
PRES
forcible
EVAC
Evacuation Input
ALARM/NORMAL
EVAC
forcible
PURG
Smoke Purge Input
ALARM/NORMAL
PURG
forcible
REL.H
RELATIVE HUMIDITY
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
OA.EN
Outdoor Air Enthalpy
OAE
OA.DP
OutsideAir Dewpoint Temp
dF
OADEWTMP
RA.RH
Return Air Rel. Humidity
%
RARH
forcible
RA.EN
Return Air Enthalpy
RAE
AIR.Q
AIR QUALITY SENSORS
IAQ.I
IAQ - Discrete Input
HIGH/LOW
IAQIN
forcible
IAQ
IAQ - PPM Return CO2
IAQ
forcible
OAQ
OAQ - PPM Return CO2
OAQ
forcible
DAQ
Diff.Air Quality in PPM
DAQ
IQ.P.O
IAQ Min.Pos. Override
%
IAQMINOV
forcible
RSET
RESET INPUTS
SA.S.R
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
SP.RS
Static Pressure Reset
SPRESET
forcible
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps
ma
IAQ_MA
OAQ.M
OAQ Milliamps
ma
OAQ_MA
SP.R.M
SP Reset milliamps
ma
SPRST_MA
DML.M
4-20 ma Demand Signal
ma
DMDLMTMA
forcible
EDR.M
EDT Reset Milliamps
ma
EDTRESMA
ORH.M
OARH Milliamps
ma
OARH_MA
RRH.M
RARH Milliamps
ma
RARH_MA
BP.M
BP Milliamps
ma
BP_MA
BP.M.T
Bldg. Pressure Trim (ma)
–2.0 - 2.0
BPMATRIM
config
SP.M
SP Milliamps
ma
SP_MA
SP.M.T
Static Press. Trim (ma)
–2.0 - 2.0
SPMATRIM
config
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...