CL-5
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
BROD
CCN BROADCST DEFINITIONS
TM.DT
CCN Time/Date Broadcast
ON/OFF
On
OAT.B
CCN OAT Broadcast
ON/OFF
Off
ORH.B
CCN OARH Broadcast
ON/OFF
Off
OAQ.B
CCN OAQ Broadcast
ON/OFF
Off
G.S.B
Global Schedule Broadcst
ON/OFF
Off
B.ACK
CCN Broadcast Ack'er
ON/OFF
Off
SC.OV
CCN SCHEDULES-OVERRIDES
SCH.N
Schedule Number
0 - 99
1
HOL.T
Accept Global Holidays?
YES/NO
No
O.T.L
Override Time Limit
0 - 4 HRS
1
OV.EX
Timed Override Hours
0 - 4 HRS
0
SPT.O
SPT Override Enabled ?
YES/NO
Yes
T58.O
T58 Override Enabled ?
YES/NO
Yes
GL.OV
Global Sched. Override ?
YES/NO
No
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ
–10-245 dF
60
SP.H.O
SPT hi alert limit/occ
–10-245 dF
85
SP.L.U
SPT lo alert limit/unocc
–10-245 dF
45
SP.H.U
SPT hi alert limit/unocc
–10-245 dF
100
SA.L.O
EDT lo alert limit/occ
–40-245 dF
40
SA.H.O
EDT hi alert limit/occ
–40-245 dF
100
SA.L.U
EDT lo alert limit/unocc
–40-245 dF
40
SA.H.U
EDT hi alert limit/unocc
–40-245 dF
100
RA.L.O
RAT lo alert limit/occ
–40-245 dF
60
RA.H.O
RAT hi alert limit/occ
–40-245 dF
90
RA.L.U
RAT lo alert limit/unocc
–40-245 dF
40
RA.H.U
RAT hi alert limit/unocc
–40-245 dF
100
R.RH.L
RARH low alert limit
0-100 %
0
R.RH.H
RARH high alert limit
0-100 %
100
SP.L
SP low alert limit
0-5 " H2O
0
SP.H
SP high alert limit
0-5 " H2O
2
BP.L
BP lo alert limit
–0.25-0.25 " H2O
-0.25
BP.H
BP high alert limit
–0.25-0.25 " H2O
0.25
IAQ.H
IAQ high alert limit
0-5000
1200
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim
–10 - 10 ^F
0
RAT.T
RAT Trim
–10 - 10 ^F
0
OAT.T
OAT Trim
–10 - 10 ^F
0
SPT.T
SPT Trim
–10 - 10 ^F
0
CTA.T
Cir A Sat.Cond.Temp Trim
–30 - 30 ^F
0
CTB.T
Cir B Sat.Cond.Temp Trim
–30 - 30 ^F
0
SP.A.T
Suct.Press.Circ.A Trim
–50 - 50 PSIG
0
SP.B.T
Suct.Press.Circ.B Trim
–50 - 50 PSIG
0
DP.A.T
Dis.Press.Circ.A Trim
–50 - 50 PSIG
0
DP.B.T
Dis.Press.Circ.B Trim
–50 - 50 PSIG
0
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean
Open/Close
Open
IGC.L
IGC Feedback - Off
Open/Close
Open
RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
Open
ECS.L
Economizer Switch - No
Open/Close
Open
SFS.L
Fan Status Sw. - Off
Open/Close
Open
DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
Open
DL2.L
Dmd.Lmt.-Dehumid - Off
Open/Close
Open
IAQ.L
IAQ Disc.Input - Low
Open/Close
Open
FSD.L
Fire Shutdown - Off
Open/Close
Open
PRS.L
Pressurization Sw. - Off
Open/Close
Open
EVC.L
Evacuation Sw. - Off
Open/Close
Open
PRG.L
Smoke Purge Sw. - Off
Open/Close
Open
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
ON/OFF
Off
METR
Metric Display
ON/OFF
Off
LANG
Language Selection
0-1(multi-text strings)
0
PAS.E
Password Enable
ENABLE/DISABLE
Enable
PASS
Service Password
0000-9999
1111
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...