![United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 178](http://html1.mh-extra.com/html/united-technologies/carrier-weathermaker-48a2/carrier-weathermaker-48a2_controls-start-up-operation-service-and-troubleshooting_4065174178.webp)
178
APPENDIX E — UPC OPEN CONTROLLER
The following section is used to configure the UPC Open.
The UPC Open controller is mounted in a separate enclosure
below the main control box.
To Address the UPC Open Controller —
The
user must give the UPC Open controller an address that is
unique on the BACnet* network. Perform the following proce-
dure to assign an address:
1. If the UPC Open controller is powered, pull the screw ter-
minal connector from the controller's power terminals la-
beled Gnd and HOT. The controller reads the address
each time power is applied to it.
2. Using the rotary switches (see Fig. G and H), set the con-
troller's address. Set the Tens (10's) switch to the tens dig-
it of the address, and set the Ones (1's) switch to the ones
digit.
As an example in Fig. G, if the controller’s address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
BACNET DEVICE INSTANCE ADDRESS — The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BAC-
net system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu
®
Tools or BACView device.
By default, a MAC address of 20 will result in a Device In-
stance of 16101 + 20 which would be a Device Instance of
1610120.
10'
s
1'
s
1
3
45
2
7
8
9
6
0
1
3
45
2
7
8
9
6
0
Fig. G — Address Rotary Switches
a48-8578
Fig. H — UPC Open Controller
8
7
6
5
4
3
2
1
09
8
7
6
5
4
3
2
1
09
BACNET
BAUD RATE
DIP
S
WITCHE
S
ADDRE
SS
ROTARY
S
WITCHE
S
POWER LED
RUN LED
ERROR LED
BACNET
CONNECTION
(BA
S
PORT)
BT4
8
5
TERMINATOR
Tx2 LED
Rx2 LED
Tx1 LED
Rx1 LED
EIA-4
8
5
JUMPER
S
a48-8579
* BACnet is a registered trademark of ASHRAE
(American Society of Heating, Refrigerating, and Air-
Conditioning Engineers).
a48-8581
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...