GENERAL AIR PRODUCTS, INC.
For Assistance Please Call 1-800 345-8207
Please keep these instructions for future reference.
OILLESSINST
REV 080906
OIL-LESS COMPRESSOR INSTRUCTION SHEETS
NOTE
This compressor is intended for installation indoors for use on dry sprinkler systems in accordance with the
Standard for Installation of Sprinkler Systems, NFPA 13 and the National Electrical Code, NFPA 70.
The compressor should be sized to restore and maintain the air pressure in the sprinkler system in
accordance with the requirements in NFPA 13.
DANGER
This compressor is not equipped and should NOT be used “as is” to supply breathing quality air.
WARNING
Motors, electrical equipment and controls can cause electrical arcs that will ignite a flammable gas or vapor.
Never operate or repair in or near a flammable gas or vapor. Never store flammable liquids or gases near
the compressor.
WARNING
These compressors are suitable for pumping only atmospheric air. As defined in Compressed Gas
Association Pamphlet G-7, page 3, atmospheric air is a mixture of elements and compounds where nitrogen
and oxygen comprise more than 99% with all other trace gases comprising less than 1%.
DO NOT USE
THIS COMPRESSOR IN CONTAMINATED ENVIRONMENTS OR FOR PUMPING MIXTURES OTHER
THAN ATMOSPHERIC AIR
WARNING
Compressed air contains liquid water and is saturated with water vapor, which can freeze. Do not connect
compressor outlet to freezer rooms or systems exposed to temperatures below freezing. If system connects
to a freezer room or area exposed to freezing temperatures, a Dry Air Pac™ should be used.
Receiving
Your compressor is inspected at the factory and
packaged to protect against shipping damage. When
the compressor is unpacked, inspect for damage or
missing parts. All claims should be settled directly
with the freight company.
WARNING:
Do not operate this compressor
if damaged during shipment, handling, or use.
Damage may result in bursting and cause
injury or property damage.
Location
NOTE
:
Do not connect compressor intake to
freezer room. – CALL 1-800-345-8207.
Locate the compressor in a clean, well-ventilated area
where the air is relatively cool, clean, and dry. A
110
o
F (35 C) maximum and 40
o
F (4.5 C) minimum
temperature for surrounding and inlet air are
recommended. Provide at least 12 to 18 inches from
any wall or other obstruction that will interfere with
airflow through the motor’s fan built into the motor.
Blocking airflow through the fan may cause the
compressor to over heat. Do not place the compressor
in an area of excessive heat, such as near a boiler.
Mounting
Riser mounted compressors may be mounted to a firm
level floor, wall or system riser. A mounting bracket
and straps are provided. Tank mounted compressors
should be bolted to the floor using the bolt holes
provided in the tank legs. Always shim the unit level
before bolting it to the floor. Vibration isolators (P/N
KVP4X4) are recommended. When using isolator
pads, do not draw bolts tight. Allow the pad to absorb
vibrations. When isolators are used, a flexible hose
(P/N P1202MP) should be installed between the
compressor and service piping.
Lubrication
NOTE
:
This compressor is designed for
non-lubricated service. Bearings are
permanently lubricated. Do not lubricate any part
of the compressor or motor.
Piping (reference “Installation
Instructions” drawings)
WARNING
Compressed air contains liquid water and is
saturated with water vapor, which can freeze. Do
not connect compressor outlet to freezer rooms
or systems exposed to temperatures below
freezing. If system connects to a freezer room or
area exposed to freezing temperatures, a Dry Air
Pac™ should be used.
Piping between the compressor, accessory items and
the sprinkler system should be at least ½” internal
APPENDIX E