3. INSTALLATION
3.1. Unpacking.
Check shipment of the UNITED Fire Systems
STANDPIPE-
PAC™
system for damage. If there is
any damage or missing parts, the transportation company's agent should make a notation to the effect on the Bill
of Lading. Claims should be settled directly with the transportation company. Verify that all parts were received in
the shipment as ordered. Contact the factory immediately if there are any missing parts or discrepancies. The
following items should be with the shipment:
STANDPIPE-P
AC™
unit
– P/N SSS-101-XX (XX = compressor size)
Manual air release bleed valve
– P/N 06-100004-000
Cap and chain for manual air release bleed valve
– P/N 06-100004-001
Nameplate for manual air release bleed valve
– P/N 10-440001-001
Standby battery (12 VDC 7.5 A-H) for control unit
– P/N 03-100005-001
Weatherproof audible / amber visual device
– P/N 03-100006-101 with amber lens attached.
Identification nameplate for audible / amber visual device
– P/N 03-100008-101
Design, installation, operation, and maintenance manual
– P/N 10-540000-001.
Auxiliary condensate drain device kit
– P/N 10-220000-100
3.2. Location.
Due consideration must be given to all of the following considerations when locating the
STANDPIPE-
PAC™
unit.
3.2.1. Temperature
.
Ensure that the
STANDPIPE-
PAC™
unit is installed in a location that will not drop below +32°F (0° C) at any
time. This may be accomplished by:
Choosing a location that will be supplied with building heat during cold weather, or;
Providing a space heater in the vicinity of the unit when cold weather is expected.
3.2.2.
Engineering Drawings (if available).
If a survey was conducted, and engineering drawings prepared, locate
all equipment per these drawings.
3.2.3.
Proximity.
The
STANDPIPE-
PAC™
unit should be installed in reasonably close proximity to the standpipe
being protected. The most logical location is in the same room as the riser. If necessary, the device may be
installed remotely. Documentation and signage should be clear to identify which equipment in remote locations
is connected together.
3.2.4.
Weight.
Ensure that the mounting surface is capable of supporting the weight of the
STANDPIPE-
PAC™
unit,
with a clear safety margin. Consult a structural engineer when necessary to verify suitability of location.
CAUTION
Understand and follow all safety recommendations when moving heavy pieces of equipment. Equipment may be
easily tipped over when moving. Failure to use caution can result in equipment damage and personal injury.
IMPORTANT
The
STANDPIPE-
PAC™
assembly is designed for use in areas where the temperature DOES NOT drop below
+32°F (0° C). DO NOT install
STANDPIPE-
PAC™
units in areas where the temperature can go below +32°F (0° C).
Failure to comply can result in unit malfunction and damage which is NOT covered by the warranty.