UNITED FIRE SYSTEMS
STANDPIPE-
PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 22
3.4.2. Startup.
STEPS TO FOLLOW FOR STANDPIPE-
PAC™ SYSTEM STARTUP
Step No.
Description
Check
When
Complete
1
Verify that all standpipe valves are CLOSED.
2
Verify that manual air release bleed valve (see Figure 2) is CLOSED.
3
Verify that the standpipe main drain valve has been opened to drain residual water from the
standpipe, and then the main drain valve has been CLOSED.
4
Verify that the Auxiliary Condensate Drain Device has been used to drain any residual water
from the piping in the vicinity of the
STANDPIPE-
PAC™,
and then Valve 1 is OPEN and
Valve 2 is CLOSED.
5
Verify that 115 VAC power is available and connected. DO NOT turn on at present.
6
Verify that lockable shutoff valve (see Figure 1 item 7) is OPEN.
7
Verify that compressor disconnect switch (see Figure 1 item 12) is OFF.
8
Open control unit (see Figure 1 item 8). Connect battery. See Figure 8.
9
Turn 115 VAC circuit breaker ON.
10
Press RESET button on control unit. AC POWER indicator should be ON.
11
ALARM indicator should be ON. Signal horn should be sounding.
12
Press SILENCE switch to acknowledge alarm. Press SILENCE switch again for 2 seconds
to silence signal horn.
13
Move compressor disconnect switch to ON. Compressor should start. Compressor is filling
standpipe with air pressure.
14
Verify that pressure gauge needle (see Figure 1 item 5) is moving upward.
15
When pressure gauge needle reaches approximately 18 PSIG, compressor should
automatically shut off.
16
Control unit should be clear, with only AC POWER indicator ON.
17
Proceed to 3.4.3
– TESTING.
IMPORTANT
The low- and high-limit pressure sensing switches, and the automatic control switch for the air compressor, have been
factory-adjusted for proper operation per this manual. DO NOT attempt to adjust these switches without authorization
from UNITED Fire Systems. These switches have factory-applied tamper seals. DO NOT break these seals.
Failure to follow these instructions can lead to improper
STANDPIPE-
PAC™
operation and will void the factory
warranty.
IMPORTANT
Pressure values indicated by the
STANDPIPE-
PAC™
pressure gauge are APPROXIMATE. Variation from nominal
values can be expected.