background image

GENERAL AIR PRODUCTS, INC. 

For Assistance Please Call 1-800 345-8207 

Please keep these instructions for future reference. 

OILLESSINST  

REV 080906 

diameter to minimize pressure drop from the 
compressor to system.  Larger pipe size may be 
required by code and may be substituted with no 
adverse effects.  Smaller line size must not be used 
and will restrict the compressor flow, lowering 
capacity and causing the compressor/motor to work 
harder, which shortens compressor/motor life.  All 
piping connected to the compressor must  be fully 
supported and not transfer any loads to the 
compressor. 
If an AMD-1 is used, allow sufficient distance 
between the compressor and AMD-1 to ensure that the 
maximum temperature at the AMD-1 is 200

o

F or less.  

When an AMD is used with riser mounted units, a 
riser mounted tank kit (p/n OLR-TK) should be 
installed to prevent short cycling the compressor.

 

All oil-less compressors include a relief valve.  For 
riser mounted models, the relief valve is installed on 
the compressor outlet.  For tank mounted models, an 
ASME Code relief valve is mounted on the 
compressor’s tank.  This valve will open at a preset 
value above the pressure switch setting to prevent 
excess tank pressure in the event of switch failure. 

WARNING: 

Do not attempt to change the 

safety relief valve setting

A manual drain is provided on the bottom of each tank 
mounted compressor.  Moisture accumulated in the 
tank, must be drained weekly.  An automatic drain , 
P/N DVA -2T, is recommended in areas of high 
humidity. 
The compressor outlet piping should contain an 
accessible drain.  As a minimum a manual drain may 
be used, but an automatic drain is recommended to 
remove excess water. 

NOTE:

 

Accumulation of condensed water in a 

system causes corrosion of components and 
reduces system capacity. 

NOTICE:

 

Warranty is void if a separate check 

valve is not installed to prevent water back flow.

 

Wiring (reference “Wiring Instructions” 
drawings) 

WARNING 

Have a qualified electrician wire the compressor 
to ensure that the supply line has the same 
characteristics (voltage, frequency and phasing) 
as the motor. Wiring must comply with all local 
and national codes. 

 

CAUTION 

Inadequate wiring size can cause insufficient 
voltage at the compressor during start -up. 
Overheating and damage to the motor and 
controls may result  

The supply wire must be of adequate size and no other 
equipment should be connected to the same line.  The 
table below lists the recommended wire size for each 
model, based on a 100’ run.  Consult factory for 
longer runs. 

MINIMUM RECOMMENDED WIRE SIZE 

MODEL 

1 PHASE 

3 PHASE 

OL11016** 

12 

N/A 

OL21533** 

10 

N/A 

OL33550** 

12 

OL42575** 

12 

OL435V75** 

12 

OL525100** 

12 

OL610V100** 

12 

OL675150** 

12 

OL900V100** 

12 

OL900V150** 

12 

OL1200V200** 

10 

10 

The motors supplied are multiple voltage motors.  A 
label on the pressure switch cover indicates the voltage 
the motor is pre-wired for.  If the supply voltage, on 
site, is different from the voltage indicated on this 
label, change the internal motor voltage connections to 
match the supply voltage.  To change internal voltage 
connections, remove the cover plate located on the 
rear or side of the motor and reconnect the wire leads 
as shown on the motor’s wiring diagram.  
On all three phase and ½ Hp and ¾ Hp single phase 
models, an arrow on the motor indicates the direction 
of rotation of the compressor.  If the compressor 
rotates in the opposite direction, reverse the rotation of 
the motor.  On single phase units, reverse motor 
rotation by interchanging the red and black motor 
leads.  Interchanging any two incoming supply wires 
reverses rotation of three phase motors. 

NOTICE: 

Single-phase oil-less 

compressors can not be operated at 208V.  
Operating the compressor at 208V voids the

 

warranty.

 

NOTICE

Single-phase motors include 

internal thermal overload protection, which has 
an automatic reset device.

   

WARNING:

  Disconnect electrical power 

before servicing to disable reset devices.  
Thermal protection can automatically start the 
motor when the protector resets. 

On single phase models, the motor is pre-wired to the 
pressure switch provided, which controls starting (cut 

Summary of Contents for STANDPIPE-PAC SSS-101

Page 1: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Page 2: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 3: ...mining Proper STANDPIPE PAC To Use 5 2 4 Example 1 6 2 5 Example 2 7 2 6 Options 8 2 6 1 Additional Audible Signals 8 2 6 2 Off Site Signaling Via Dialer 8 3 INSTALLATION 3 1 Unpacking 9 3 2 Location...

Page 4: ...32 4 4 5 To Refill Standpipe With Air Pressure After Fire Department Use 33 4 4 6 To Test Standpipe with Water Pressure 34 5 MAINTENANCE 36 5 1 Weekly 37 5 2 Monthly 37 5 3 Quarterly 38 APPENDICES App...

Page 5: ...formation is provided for the safety of installers operators and users of the UNITED Fire Systems STANDPIPE PAC equipment Carefully read understand and follow instructions identified by these symbols...

Page 6: ...ate at the time of publication but the data is published and presented without any guarantee or warranty whatsoever UNITED Fire Systems disclaims any liability for any use that may be made of the data...

Page 7: ...STANDPIPE PAC without instructions from UNITED Fire Systems the STANDPIPE PAC is not covered If you break tamper seals applied by UNITED Fire Systems the sealed parts are not covered Any problem that...

Page 8: ...air dryer dries the compressed air before entry into the standpipe as required by Boston FD TCM3 51725 3 Low limit pressure sensing switch This switch senses when the pressure in the standpipe drops b...

Page 9: ...side the location of the STANDPIPE PAC and wire the device in accordance with the instructions in this manual 17 An auxiliary condensate drain device This device permits manual draining of water in th...

Page 10: ...2 00 P N 10 540101 001 Page 3 INSTRUCTION NAMEPLATE 15 MANUAL AIR RELEASE BLEED VALVE CAP AND CHAIN Figure 2 Manual Air Release Bleed Valve Figure 4 Auxiliary Condensate Drain Device 17 AUXILIARY COND...

Page 11: ...determined by multiplying the length of each pipe by size by the internal volume per foot in gallons Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 1 1 2 X 0 106 2 X 0 174 2 1 2 X 0 2...

Page 12: ...the desired fill time at the bottom of the graph 2 3 2 Find the standpipe internal volume at the left of the graph 2 3 3 Determine the intersection of the lines from these two values 2 3 4 Choose the...

Page 13: ...101 001 Page 6 2 4 Example 1 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 6 750 X 1 500 1125 TOTAL 1125 gallons Required work can be performed in 1 2 hour 30 minutes so a fill time o...

Page 14: ...e 2 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 2 80 X 0 174 14 6 100 X 1 500 150 8 550 X 2 600 1430 TOTAL 1594 gallons Fill time of 1 hour 60 minutes required Figure 7 Design Examp...

Page 15: ...his manual for further information See Paragraph 3 3 5 5 for installation instructions 2 6 2 Off Site Signaling Via Dialer The STANDPIPE PAC control unit is equipped with a built in dialer for off sit...

Page 16: ...3 2 1 Temperature Ensure that the STANDPIPE PAC unit is installed in a location that will not drop below 32 F 0 C at any time This may be accomplished by Choosing a location that will be supplied wit...

Page 17: ...t least 3 feet of clearance for personnel to access equipment for maintenance 3 3 Installation 3 3 1 Mounting See Figure 8 Mount the STANDPIPE PAC in the chosen mounting location It is strongly recomm...

Page 18: ...regular basis permitting any water accumulation or pooled water from testing to drain Dry standpipes installed with supervisory systems shall be installed per Figure 9 above The diagram indicates sev...

Page 19: ...and discard plastic plug from device inlet Valve 1 3 See Figure 10 Attach a inch close pipe nipple and the bull of a inch pipe tee to device inlet Valve 1 4 Install a convenient length of inch thread...

Page 20: ...1 60 3 4 10 6 0 7 11 3 3 3 5 3 Power Wiring See Table 3 Choose minimum conductor sizes and overcurrent protective device based on total current shown in table Connect power in junction box provided fo...

Page 21: ...NDPIPE PAC MODEL SSS 101 DESIGN INSTALLATION OPERATION AND MAINTENANCE MANUAL REVISION 2 00 P N 10 540101 001 Page 14 3 3 5 4 Battery Wiring See Figure 11 DO NOT connect battery until commissioning Fi...

Page 22: ...5 5 4 Optional Signaling Devices If additional audible devices are desired connect these devices to the notification appliance circuit serving the signal horn on the STANDPIPE PAC unit See Appendix D...

Page 23: ...9 optional signal horns Maximum Current Draw FOR ALL external Signal Horns INCLUDING required external audible visual device NOT including factory installed signal horn 1 0 A Maximum Length Of Notific...

Page 24: ...rn assembly on STANDPIPE PAC En End of Line Resistor 3 See Figure 13 2 Visually inspect Signal Horn base plate connections Locate positive and negative terminals on base plate NOTE RED wire connects t...

Page 25: ...all raceway from factory installed Signal Horn back box to additional Signal Horn NOTE See Table 4 for distance limitations 8 See Figure 13 6 Run 14 AWG Solid wires from additional Signal Horn through...

Page 26: ...Connect wires at additional Signal Horns IMPORTANT Do not branch Signal Horn circuit Run circuit from the first Signal Horn to the second Signal Horn then the second Signal Horn to the third and so on...

Page 27: ...ent capacity of the circuit when adding additional horns to the STANDPIPE PAC Each additional horn adjusted to FULL VOLUME draws 0 047 amps As noted on page 1 the current for all external devices incl...

Page 28: ...and 18 PSIG should be adequate for supervising the standpipe and providing prompt signaling if a valve is opened or a portion of the standpipe is removed Setting the HIGH pressure signal at 23 PSIG 2...

Page 29: ...ON 10 Press RESET button on control unit AC POWER indicator should be ON 11 ALARM indicator should be ON Signal horn should be sounding 12 Press SILENCE switch to acknowledge alarm Press SILENCE switc...

Page 30: ...lear and ALARM indicator should be OFF 12 When pressure gauge needle reaches approximately 18 PSIG compressor should automatically shut off HIGH LIMIT PRESSURE SENSING SWITCH TEST 13 Verify that compr...

Page 31: ...115 VAC not properly connected in junction box Properly connect power in junction box 3 3 5 3 STANDPIPE PAC does not build sufficient pressure in standpipe less than 7 PSIG One or more outlet valves o...

Page 32: ...nstalled in area where temperature cannot go below 32 degrees F Color of beads in air dryer has changed Air dryer beads have absorbed water to their capacity Compare color of beads to decal on side of...

Page 33: ...unit outlet lockable shutoff valve OPEN Has the battery been connected to the control unit Has 115 VAC power been turned ON Has the control unit RESET button been operated and is the control unit AC P...

Page 34: ...device been operated and is the pressure gauge needle moving UP When the pressure gauge needle reaches approximately 23 PSIG does the control unit ALARM indicator come ON and do the signals operate Ha...

Page 35: ...toff valve Is the control unit door locked Have the control unit keys lockable shutoff valve key s and UFS Manual P N 10 540101 001 been given to the responsible individual at the job site If the cont...

Page 36: ...s a yellow LED visible with unit door closed or open indicating trouble with the backup battery 4 1 3 5 Visual Indicator SYSTEM TRBL This is a yellow LED visible with unit door closed or open indicati...

Page 37: ...ON INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge Indicating between 13 and 18 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE Off Visual Indicator COMM FAIL Off Visual Ind...

Page 38: ...ignal Operation High Pressure In Standpipe If pressure increases in standpipe above 25 PSIG the following will be indicated HIGH PRESSURE IN STANDPIPE INDICATOR or CONTROL ITEM STATUS Visual Indicator...

Page 39: ...sor Disconnect Switch ON Control Test Service Device Not Operated 4 4 2 To Silence Piezo Sounder Press ACKNOWLEDGE SILENCE HOLD 2 SEC pushbutton once 4 4 3 To Silence Signal Horns Press ACKNOWLEDGE SI...

Page 40: ...ating less than 7 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE ON Visual Indicator COMM FAIL Off Visual Indicator BATT FAULT Off Visual Indicator SYSTEM TRBL Off Visual Indicator SUPERVIS...

Page 41: ...points or traps without drains CLOSE Lockable Shutoff Valve BEFORE testing standpipe with water pressure Perform pressure test Use main drain and all drainage valves at low points to drain all water f...

Page 42: ...ry Condensate Drain Device to drain all water from piping in the vicinity of the STANDPIPE PAC It may take time for water to migrate from upper floors Allow sufficient time with drains open for all wa...

Page 43: ...PAC pressure gauge are APPROXIMATE Variation from nominal values can be expected IMPORTANT The STANDPIPE PAC unit including control unit has been pre wired and programmed at the factory for proper ope...

Page 44: ...in intact and connected to valve Valve OPEN Cap Disconnected or Missing If valve is OPEN CLOSE valve tightly If cap is disconnected re connect If cap is missing contact service provider for replacemen...

Page 45: ...For this reason it is recommended that the dryer desiccant be replaced quarterly NOTE Refer to Figure 15 1 Have Qty 1 UFS P N 21 100000 100 Replacement Desiccant available 2 Notify local personnel tha...

Page 46: ...se Qty 1 UFS P N 21 100000 100 13 Carefully align and insert desiccant bowl back into assembly until it is flush against air dryer cap 14 Depress tab marked PUSH and turn connecting ring until connect...

Page 47: ...compressor disconnect switch to OFF 3 Use 5 32 hex key to remove 2 hex screws holding black filter housing in place 4 Remove filter housing 5 Remove and discard existing foam filter element 6 Replace...

Page 48: ...ew filter 7 Monthly Has the Auxiliary Condensate Drain Device been properly used to remove water from the piping in the vicinity of the STANDPIPE PAC 8 Quarterly Has the HIGH PRESSURE signal been chec...

Page 49: ...LL CORRECTIONS REPAIRS MADE LIST ALL CORRECTIONS REPAIRS NEEDED NOTES PRINT NAME SIGNATURE DATE INSPECTOR CUSTOMER INSPECTION MAINTENANCE CHECKLIST STANDPIPE PAC SUPERVISORY SYSTEM UFS 236 REVISION 2...

Page 50: ...N 1 Remove Cover Cover is held on by two tamper resistant screws Removal key is en closed with pressure switch 2 Mounting the Switch The device is designed to be mounted in the upright or horizontal p...

Page 51: ...D770 08 00 2 I56 0551 009R System Sensor 2014 System Sensor warrants its enclosed pressure switch to be free from defects in materials and workmanship under normal use and service for a period of thr...

Page 52: ...to be mounted in the upright position side mounting is also acceptable Locate it where vibration shock and mechanical loading are minimal Refer to piping diagram above Fig 2 and 3 a Mount the device...

Page 53: ...W TRIP POINT SW1 SW2 MODELS EPS40 2 EPS120 2 SWITCHES AT HIGH TRIP POINT SW1 SW2 B COM A B COM A B COM A A COM B A COM B A COM B DUAL SWITCH MODEL EPS40 2 AND EPS120 2 1 Install pressure switch as sta...

Page 54: ...tion Perform pre ventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bimonthly Install a back up control for all critical applications where control...

Page 55: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 56: ...d the life of the coalescing element Specifications X06 X03 Plastic Bowl X03 Metal Bowl X04 X25 Metal Bowl Maximum Pressure 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150...

Page 57: ...ge meaning dry to dark green meaning wet 3 By installing two or more units in parallel higher dry airflows can be achieved Maintenance 1 The only servicing required for silica gel units is when the de...

Page 58: ...95 623 1 8 Clamp Ring GRP 96 404 1 GRP 96 404 1 NNR Not normally replaced The moisture indicator contains a weep orifice to provide an air sample to the moisture indicating paper Air leakage from thi...

Page 59: ...rated plastic bowl with a bowl or a new plastic bowl and bowl guard CAUTION Except as otherwise specified by the manufacturer this product is specifically designed for compressed air service and use w...

Page 60: ...ould be settled directly with the freight company WARNING Do not operate this compressor if damaged during shipment handling or use Damage may result in bursting and cause injury or property damage Lo...

Page 61: ...ed electrician wire the compressor to ensure that the supply line has the same characteristics voltage frequency and phasing as the motor Wiring must comply with all local and national codes CAUTION I...

Page 62: ...RCE THEN RELEASE ALL PRESSURE FROM THE SYSTEM BEFORE ATTEMPTING TO INSTALL SERVICE RELOCATE OR PERFORM ANY SERVICE The following instructions are based on NORMAL operation If the compressor is in an e...

Page 63: ...voltage to start motor Increase wire size if necessary to lower voltage drop 2 Consult factory adjust or replace 3 Be sure fuses and heaters are rated properly 4 Add receiver vessel or increase pipe...

Page 64: ...NGLE PHASE WIRING INSTRUCTIONS OIL LESS COMPRESSOR NOTE MOST MOTORS ARE MULTIPLE VOLTAGE CHECK NAMEPLATE AND VERIFY CORRECT INTERNAL CONNECTIONS FOR VOLTAGE BEING SUPPLIED TO UNIT FEEDER WIRE SIZE MUS...

Page 65: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 66: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 67: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Reviews: