3.3.4. Auxiliary Condensate Drain Device
1. Determine the installation location of the Auxiliary Condensate Drain Device:
a. Locate the device in close proximity to the outlet of the
STANDPIPE-
PAC™.
b. The location of the
STANDPIPE-
PAC™
and the Auxiliary Condensate Drain Device MUST be in an area
protected from freezing temperatures (over +32°F (0° C)).
c. The device MUST be installed vertically
– see Figure 9 and Figure 10.
d. No separate bracket is necessary
– the inlet piping connection should be satisfactory to hold the device in
place.
2. Remove and discard plastic plug from device inlet (Valve 1).
3. See Figure 10. Attach a ½ inch close pipe nipple and the bull of a ½ inch pipe tee to device inlet.(Valve 1)
4. Install a convenient length of ½ inch threaded pipe between the outlet of the
STANDPIPE-
PAC™
and the run of
the tee attached to the device inlet.
5. See Figure 10. Connect ½ inch pipe to the remaining run of the tee attached to the device and the inlet to the dry
standpipe. Pitch the pipe to drain away from the device.
6. See Figure 4. Attach Instruction Nameplate to wall in close proximity to device.
IMPORTANT
The Auxiliary Condensate Drain Device does NOT take the place of a standpipe system main drain. Ensure that a
main drain valve is properly installed at the lowest point of the standpipe, in an accessible area, where all the water
from the standpipe may be properly drained.
Figure 10
– Auxiliary Condensate Drain Device