UNITED FIRE SYSTEMS
STANDPIPE-
PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 10
3.2.5.
Noise.
The
STANDPIPE-
PAC™
unit
does emit noise when running. Consideration should be given to locating
equipment where normal operating noise does not interfere with building operations.
3.2.6.
Clearance.
Sufficient clearance should be available after installation for maintenance operations to take place.
Leave at least (3) feet of clearance for personnel to access equipment for maintenance.
3.3. Installation.
3.3.1.
Mounting.
See Figure 8.
Mount the
STANDPIPE-
PAC™
in the chosen mounting location.
It is strongly recommended that the unit be mounted on a wall.
The unit weighs approximately 86 lbs. Choose a wall with construction capable of supporting this weight, with
a reasonable safety margin.
Use good standard practice and appropriate fasteners.
The back board may be drilled as needed for mounting. Do not drill holes too close to corners.
Leave a minimum of 3 feet of clearance in front of unit for personnel to perform maintenance.
Figure 8
– Dimensions –
STANDPIPE-
PAC™
Unit