background image

GROUND
SCREW

CO

M

B

A

COMMON
TERMINALS

BREAK WIRE AS SHOWN FOR

SUPERVISION OF CONNECTION.

DO NOT ALLOW STRIPPED WIRE

LEADS TO EXTEND BEYOND

SWITCH HOUSING. DO NOT

LOOP WIRES.

SWITCH #1

SWITCH #2

SW

ITC

H #

2

LOCKING
SCREW

TERMINAL “A”

TERMINAL “B”

D770-17-00 

2 I56-0986-008R

TABLE 2.

FACTORY SETTINGS (PSI)

MODEL

Fall SW2

(Low Switch)

Rise SW1

(Hi Switch)

Nominal

EPS40-1

EPS40-2

EPS120-1

EPS120-2

30

±

 1.5

30

±

 1.5

––

115

101.5 - 112.5

101.5 - 112.5

117.5 - 128.5

115

––

40

50

±

 2.5

40

SINGLE-SWITCH MODEL — EPS40-1 AND EPS120-1

1.   Install pressure switch as stated in “INSTALLATION” portion of instruc-

tion manual. Attach pressure test source to system.

2.   Back off locking screw (see Fig. 4) to allow main adjustment wheel to 

rotate freely.

3.   Test the switch for the set point by introducing 40 PSI pressure from the 

pressure test source for the EPS40-1 (115 PSI for the EPS120-1). Decrease 
pressure slowly until the switch trips. Rotate main adjustment wheel, 
Figure 5, (counterclockwise to increase pressure) and retest by first intro-
ducing a higher pressure than desired and slowly reducing pressure until 
the switch trips. Repeat process until switch trip point is at desired pres-
sure setting. Each number represents an approximate trip point change 
of 1.8 PSI for the EPS40-1 and 6.6 PSI for the EPS120-1. For each 

1

/

2

 

rotation of the adjustment wheel, the trip point setting changes by ap-
proximately 11 PSI for the EPS40-1 and 40 PSI for the EPS120-1.

4.  Retest the set point several times to ensure accuracy of setting.
5.  Re-seat locking screw.

C0141-01

FIGURE 3. TYPICAL PIPING DIAGRAM FOR EPS120-1, EPS120-2

FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS40-1, EPS40-2

DRY

PIPE

VALVE

OS & Y

VALVE

WATER

BY-PASS

TEST

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER

MOTOR

GONG

CHECK

VALVE

EPS40

CHECK

VALVE

AIR LINE

SHUT-OFF

VALVE

INSTALL

BLEEDER

VALVE FOR

TESTING

EPS10

DRY SYSTEM

WIRE TO SUPERVISORY

CIRCUIT OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

TO

SPRINKLER

SYSTEM

FIGURE 4. SWITCH LOCATION:

W0185-01

W0186-00

TABLE 1. ELECTRICAL CONNECTIONS (REFERENCED AT FACTORY 
SETTINGS):

MODELS EPS40-1, EPS120-1

SWITCH AT NORMAL SYSTEM PRESSURE

SWITCH AT TRIP POINT

B

COM

A

A

COM

B

SWITCH 1

SW2

SW1

SWITCHES AT NORMAL SYSTEM PRESSURE

SWITCHES AT LOW TRIP POINT

SW1

SW2

MODELS EPS40-2, EPS120-2

SWITCHES AT HIGH TRIP POINT

SW1

SW2

B

COM

A

B

COM

A

B

COM

A

A

COM

B

A

COM

B

A

COM

B

DUAL-SWITCH MODEL — EPS40-2 AND EPS120-2

1.   Install pressure switch as stated in “INSTALLATION” portion of instruc-

tion manual. Attach pressure test source to system.

2.   Back out the locking screw (see Fig. 4) to allow main adjustment wheel 

to turn freely.

3.  

Option 1: Adjust nominal pressure setting without affecting PSI window.

 

a)  Adjust main adjustment wheel (see Fig. 5) to desired setting using 

pressure source (i.e., valve or air maintenance device).

 

b)  Turn main adjustment wheel counterclockwise to increase (see arrow 

on mounting base) or clockwise to decrease pressure. Each number 
on main adjust wheel represents an approximate window shift of 1.8 
psi for EPS40-2 and 6.6 psi for EPS120-2. For each 

1

/

2

 rotation of the 

adjustment wheel the window changes by approximately 11 psi for 
EPS40-2 and 40 psi for EPS120-2.

 

c)  Retest the set point several times to ensure the accuracy of the setting.

 

Option 2:  Adjust pressure window size and nominal setting of pres-

sure window.

 

a)  Adjust main adjustment wheel (see Fig. 5) until high switch (SW1) 

trips at desired pressure using pressure test source (valve or air main-
tenance device).

 

b)  Refer to step B from Option 1.

 

c) Decrease pressure until the low switch trips (SW2).

 

d)   Adjust 

1

/

4

˝ low pressure hex head nut (see Fig. 5) to either increase 

(counterclockwise) or decrease (clockwise) the window size (the low 
switch will be affected).

 

e)  The approximate sensitivity of the hex screw adjustment: 

1

/

2  

turn

 

=5 

psi. A maximum of 30 psi is attainable.

4.   Retest the set points several times to ensure the accuracy of the settings, 

and adjust as necessary.

5.  Re-seat locking screw.
NOTE: EPS40 models are able to be set to a range within 8-100psi only when 
used with Victaulic series 768 and 769 FireLock NXT valves pre-set for use 
with low pressure actuators.  When used on Victaulic  series 768 and 769 
FireLock NXT all units must be 100% tested to verify pressure setting.  Both 
the main adjustment wheel and low pressure adjusting screw (See Figure 5) 
need to be customer set and tested to insure proper functionality.  For pres-
sure setting instructions refer to Installation section for dual switch models in 
this manual.

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

AIR

PRESSURE

SUPPLY

BLEEDER

TEST

VALVE

EPS120

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

C0142-01

Summary of Contents for STANDPIPE-PAC SSS-101

Page 1: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Page 2: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 3: ...mining Proper STANDPIPE PAC To Use 5 2 4 Example 1 6 2 5 Example 2 7 2 6 Options 8 2 6 1 Additional Audible Signals 8 2 6 2 Off Site Signaling Via Dialer 8 3 INSTALLATION 3 1 Unpacking 9 3 2 Location...

Page 4: ...32 4 4 5 To Refill Standpipe With Air Pressure After Fire Department Use 33 4 4 6 To Test Standpipe with Water Pressure 34 5 MAINTENANCE 36 5 1 Weekly 37 5 2 Monthly 37 5 3 Quarterly 38 APPENDICES App...

Page 5: ...formation is provided for the safety of installers operators and users of the UNITED Fire Systems STANDPIPE PAC equipment Carefully read understand and follow instructions identified by these symbols...

Page 6: ...ate at the time of publication but the data is published and presented without any guarantee or warranty whatsoever UNITED Fire Systems disclaims any liability for any use that may be made of the data...

Page 7: ...STANDPIPE PAC without instructions from UNITED Fire Systems the STANDPIPE PAC is not covered If you break tamper seals applied by UNITED Fire Systems the sealed parts are not covered Any problem that...

Page 8: ...air dryer dries the compressed air before entry into the standpipe as required by Boston FD TCM3 51725 3 Low limit pressure sensing switch This switch senses when the pressure in the standpipe drops b...

Page 9: ...side the location of the STANDPIPE PAC and wire the device in accordance with the instructions in this manual 17 An auxiliary condensate drain device This device permits manual draining of water in th...

Page 10: ...2 00 P N 10 540101 001 Page 3 INSTRUCTION NAMEPLATE 15 MANUAL AIR RELEASE BLEED VALVE CAP AND CHAIN Figure 2 Manual Air Release Bleed Valve Figure 4 Auxiliary Condensate Drain Device 17 AUXILIARY COND...

Page 11: ...determined by multiplying the length of each pipe by size by the internal volume per foot in gallons Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 1 1 2 X 0 106 2 X 0 174 2 1 2 X 0 2...

Page 12: ...the desired fill time at the bottom of the graph 2 3 2 Find the standpipe internal volume at the left of the graph 2 3 3 Determine the intersection of the lines from these two values 2 3 4 Choose the...

Page 13: ...101 001 Page 6 2 4 Example 1 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 6 750 X 1 500 1125 TOTAL 1125 gallons Required work can be performed in 1 2 hour 30 minutes so a fill time o...

Page 14: ...e 2 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 2 80 X 0 174 14 6 100 X 1 500 150 8 550 X 2 600 1430 TOTAL 1594 gallons Fill time of 1 hour 60 minutes required Figure 7 Design Examp...

Page 15: ...his manual for further information See Paragraph 3 3 5 5 for installation instructions 2 6 2 Off Site Signaling Via Dialer The STANDPIPE PAC control unit is equipped with a built in dialer for off sit...

Page 16: ...3 2 1 Temperature Ensure that the STANDPIPE PAC unit is installed in a location that will not drop below 32 F 0 C at any time This may be accomplished by Choosing a location that will be supplied wit...

Page 17: ...t least 3 feet of clearance for personnel to access equipment for maintenance 3 3 Installation 3 3 1 Mounting See Figure 8 Mount the STANDPIPE PAC in the chosen mounting location It is strongly recomm...

Page 18: ...regular basis permitting any water accumulation or pooled water from testing to drain Dry standpipes installed with supervisory systems shall be installed per Figure 9 above The diagram indicates sev...

Page 19: ...and discard plastic plug from device inlet Valve 1 3 See Figure 10 Attach a inch close pipe nipple and the bull of a inch pipe tee to device inlet Valve 1 4 Install a convenient length of inch thread...

Page 20: ...1 60 3 4 10 6 0 7 11 3 3 3 5 3 Power Wiring See Table 3 Choose minimum conductor sizes and overcurrent protective device based on total current shown in table Connect power in junction box provided fo...

Page 21: ...NDPIPE PAC MODEL SSS 101 DESIGN INSTALLATION OPERATION AND MAINTENANCE MANUAL REVISION 2 00 P N 10 540101 001 Page 14 3 3 5 4 Battery Wiring See Figure 11 DO NOT connect battery until commissioning Fi...

Page 22: ...5 5 4 Optional Signaling Devices If additional audible devices are desired connect these devices to the notification appliance circuit serving the signal horn on the STANDPIPE PAC unit See Appendix D...

Page 23: ...9 optional signal horns Maximum Current Draw FOR ALL external Signal Horns INCLUDING required external audible visual device NOT including factory installed signal horn 1 0 A Maximum Length Of Notific...

Page 24: ...rn assembly on STANDPIPE PAC En End of Line Resistor 3 See Figure 13 2 Visually inspect Signal Horn base plate connections Locate positive and negative terminals on base plate NOTE RED wire connects t...

Page 25: ...all raceway from factory installed Signal Horn back box to additional Signal Horn NOTE See Table 4 for distance limitations 8 See Figure 13 6 Run 14 AWG Solid wires from additional Signal Horn through...

Page 26: ...Connect wires at additional Signal Horns IMPORTANT Do not branch Signal Horn circuit Run circuit from the first Signal Horn to the second Signal Horn then the second Signal Horn to the third and so on...

Page 27: ...ent capacity of the circuit when adding additional horns to the STANDPIPE PAC Each additional horn adjusted to FULL VOLUME draws 0 047 amps As noted on page 1 the current for all external devices incl...

Page 28: ...and 18 PSIG should be adequate for supervising the standpipe and providing prompt signaling if a valve is opened or a portion of the standpipe is removed Setting the HIGH pressure signal at 23 PSIG 2...

Page 29: ...ON 10 Press RESET button on control unit AC POWER indicator should be ON 11 ALARM indicator should be ON Signal horn should be sounding 12 Press SILENCE switch to acknowledge alarm Press SILENCE switc...

Page 30: ...lear and ALARM indicator should be OFF 12 When pressure gauge needle reaches approximately 18 PSIG compressor should automatically shut off HIGH LIMIT PRESSURE SENSING SWITCH TEST 13 Verify that compr...

Page 31: ...115 VAC not properly connected in junction box Properly connect power in junction box 3 3 5 3 STANDPIPE PAC does not build sufficient pressure in standpipe less than 7 PSIG One or more outlet valves o...

Page 32: ...nstalled in area where temperature cannot go below 32 degrees F Color of beads in air dryer has changed Air dryer beads have absorbed water to their capacity Compare color of beads to decal on side of...

Page 33: ...unit outlet lockable shutoff valve OPEN Has the battery been connected to the control unit Has 115 VAC power been turned ON Has the control unit RESET button been operated and is the control unit AC P...

Page 34: ...device been operated and is the pressure gauge needle moving UP When the pressure gauge needle reaches approximately 23 PSIG does the control unit ALARM indicator come ON and do the signals operate Ha...

Page 35: ...toff valve Is the control unit door locked Have the control unit keys lockable shutoff valve key s and UFS Manual P N 10 540101 001 been given to the responsible individual at the job site If the cont...

Page 36: ...s a yellow LED visible with unit door closed or open indicating trouble with the backup battery 4 1 3 5 Visual Indicator SYSTEM TRBL This is a yellow LED visible with unit door closed or open indicati...

Page 37: ...ON INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge Indicating between 13 and 18 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE Off Visual Indicator COMM FAIL Off Visual Ind...

Page 38: ...ignal Operation High Pressure In Standpipe If pressure increases in standpipe above 25 PSIG the following will be indicated HIGH PRESSURE IN STANDPIPE INDICATOR or CONTROL ITEM STATUS Visual Indicator...

Page 39: ...sor Disconnect Switch ON Control Test Service Device Not Operated 4 4 2 To Silence Piezo Sounder Press ACKNOWLEDGE SILENCE HOLD 2 SEC pushbutton once 4 4 3 To Silence Signal Horns Press ACKNOWLEDGE SI...

Page 40: ...ating less than 7 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE ON Visual Indicator COMM FAIL Off Visual Indicator BATT FAULT Off Visual Indicator SYSTEM TRBL Off Visual Indicator SUPERVIS...

Page 41: ...points or traps without drains CLOSE Lockable Shutoff Valve BEFORE testing standpipe with water pressure Perform pressure test Use main drain and all drainage valves at low points to drain all water f...

Page 42: ...ry Condensate Drain Device to drain all water from piping in the vicinity of the STANDPIPE PAC It may take time for water to migrate from upper floors Allow sufficient time with drains open for all wa...

Page 43: ...PAC pressure gauge are APPROXIMATE Variation from nominal values can be expected IMPORTANT The STANDPIPE PAC unit including control unit has been pre wired and programmed at the factory for proper ope...

Page 44: ...in intact and connected to valve Valve OPEN Cap Disconnected or Missing If valve is OPEN CLOSE valve tightly If cap is disconnected re connect If cap is missing contact service provider for replacemen...

Page 45: ...For this reason it is recommended that the dryer desiccant be replaced quarterly NOTE Refer to Figure 15 1 Have Qty 1 UFS P N 21 100000 100 Replacement Desiccant available 2 Notify local personnel tha...

Page 46: ...se Qty 1 UFS P N 21 100000 100 13 Carefully align and insert desiccant bowl back into assembly until it is flush against air dryer cap 14 Depress tab marked PUSH and turn connecting ring until connect...

Page 47: ...compressor disconnect switch to OFF 3 Use 5 32 hex key to remove 2 hex screws holding black filter housing in place 4 Remove filter housing 5 Remove and discard existing foam filter element 6 Replace...

Page 48: ...ew filter 7 Monthly Has the Auxiliary Condensate Drain Device been properly used to remove water from the piping in the vicinity of the STANDPIPE PAC 8 Quarterly Has the HIGH PRESSURE signal been chec...

Page 49: ...LL CORRECTIONS REPAIRS MADE LIST ALL CORRECTIONS REPAIRS NEEDED NOTES PRINT NAME SIGNATURE DATE INSPECTOR CUSTOMER INSPECTION MAINTENANCE CHECKLIST STANDPIPE PAC SUPERVISORY SYSTEM UFS 236 REVISION 2...

Page 50: ...N 1 Remove Cover Cover is held on by two tamper resistant screws Removal key is en closed with pressure switch 2 Mounting the Switch The device is designed to be mounted in the upright or horizontal p...

Page 51: ...D770 08 00 2 I56 0551 009R System Sensor 2014 System Sensor warrants its enclosed pressure switch to be free from defects in materials and workmanship under normal use and service for a period of thr...

Page 52: ...to be mounted in the upright position side mounting is also acceptable Locate it where vibration shock and mechanical loading are minimal Refer to piping diagram above Fig 2 and 3 a Mount the device...

Page 53: ...W TRIP POINT SW1 SW2 MODELS EPS40 2 EPS120 2 SWITCHES AT HIGH TRIP POINT SW1 SW2 B COM A B COM A B COM A A COM B A COM B A COM B DUAL SWITCH MODEL EPS40 2 AND EPS120 2 1 Install pressure switch as sta...

Page 54: ...tion Perform pre ventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bimonthly Install a back up control for all critical applications where control...

Page 55: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 56: ...d the life of the coalescing element Specifications X06 X03 Plastic Bowl X03 Metal Bowl X04 X25 Metal Bowl Maximum Pressure 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150...

Page 57: ...ge meaning dry to dark green meaning wet 3 By installing two or more units in parallel higher dry airflows can be achieved Maintenance 1 The only servicing required for silica gel units is when the de...

Page 58: ...95 623 1 8 Clamp Ring GRP 96 404 1 GRP 96 404 1 NNR Not normally replaced The moisture indicator contains a weep orifice to provide an air sample to the moisture indicating paper Air leakage from thi...

Page 59: ...rated plastic bowl with a bowl or a new plastic bowl and bowl guard CAUTION Except as otherwise specified by the manufacturer this product is specifically designed for compressed air service and use w...

Page 60: ...ould be settled directly with the freight company WARNING Do not operate this compressor if damaged during shipment handling or use Damage may result in bursting and cause injury or property damage Lo...

Page 61: ...ed electrician wire the compressor to ensure that the supply line has the same characteristics voltage frequency and phasing as the motor Wiring must comply with all local and national codes CAUTION I...

Page 62: ...RCE THEN RELEASE ALL PRESSURE FROM THE SYSTEM BEFORE ATTEMPTING TO INSTALL SERVICE RELOCATE OR PERFORM ANY SERVICE The following instructions are based on NORMAL operation If the compressor is in an e...

Page 63: ...voltage to start motor Increase wire size if necessary to lower voltage drop 2 Consult factory adjust or replace 3 Be sure fuses and heaters are rated properly 4 Add receiver vessel or increase pipe...

Page 64: ...NGLE PHASE WIRING INSTRUCTIONS OIL LESS COMPRESSOR NOTE MOST MOTORS ARE MULTIPLE VOLTAGE CHECK NAMEPLATE AND VERIFY CORRECT INTERNAL CONNECTIONS FOR VOLTAGE BEING SUPPLIED TO UNIT FEEDER WIRE SIZE MUS...

Page 65: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 66: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 67: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Reviews: