background image

2

   d. See  replacement  parts  list  for  specifics  on  kit  numbers  for  

  replacement desiccant.

  3. 

Desiccant regeneration:

   a. 

— For silica gel (“000”) units:

  

Pour out used Pink desiccant 

onto  flat  pan.  Place  Pink  desiccant  in  350°F  (176°C)  oven  for 

approximately  three  hours  or  until  the  desiccant  color  has 

changed back to Blue.

      — For  13x  molecular  sieve  (“X00”)  units  cannot  be  

    regenerated. See page 5 for replacement kits.

      — For  4A  molecular  sieve  (“U00”)  units:    Pour  out  used  

    desiccant onto flat pan. Place desiccant in 600°F (316°C)  

    oven for up to a maximum of 3 hours. 

   b. Remove desiccant from oven and allow to cool down to ambient  

  temperature.

   c.  Pour  desiccant  back  into  unit  bowl,  periodically  shaking  and  

  tapping to settle the desiccant.

  4.  Replace bowl and bowl guard, or metal bowl, and clamp ring onto 

the  unit.  Be  sure  clamp  ring  is  securely  locked  in  place  before 

repressurizing the unit.

Models X06, X03, X04, and X25

Inner

Step

1/8"

X03 / X04 / X25

Figure 3

Bowl

Clamp

Ring

X03 / X04 / X25

Figure 1

Keep 

Covered

Figure 2

•  Coalescing Filter:  

Should be used prior to the manual desiccant 

dryer in any lubricated compressor system which does not utilize 

a system coalescing filter. The coalescing filter removes oil from 

the  compressed  air,  which  prevents  the  oil  from  coating  the 

silica  gel  or  mole  sieve  and  destroying  its  ability  to  dry  the  air. 

Oil  contaminated  desiccant  must  be  replaced  and  disposed  of 

properly, as it cannot be regenerated.

•  Afterfilter:   

Should  be  used  after  the  manual  desiccant  dryer 

in  any  system  where  any  amount  of  desiccant  dust,  however 

insignificant,  is  undesirable.  The  afterfilter  prevents  the  very 

slight desiccant dusting, which occurs over time, from proceeding 

downstream into the compressed air system.

•   Pre-Dryers:  

Both the silica gel and mole sieve manual desiccant 

dryers can have their drying lives extended through the use of a 

pre-dryer.  The  silica  gel  (“000”/“M00”)  models  will  typically  last 

over three times as long if a refrigerated air dryer is placed in the 

compressed air system prior to it. (A plant air system refrigerated 

dryer will provide the same extended life.) The mole sieve (“U00”/

“MU0”) models will typically last three times as long if a silica gel 

(“000”/“M00”) model dryer installed prior to the mole sieve dryer. 

(A plant air system desiccant dryer will provide the same extended 

life.) Users of either type of manual desiccant dryer who expect 

a  high  air  flow  demand  may  wish  to  consider  using  a  pre-dryer. 

Please see page 4 for exact model recommendations.

Operation

  1. The  silica  gel  desiccant,  when  visible  through  the  clear  

polycarbonate  plastic  bowl,  contains  a  color  indicator.  It  changes 

from Blue (meaning dry) to Pink (meaning wet) to indicate the need 

to  replace  or  regenerate  the  desiccant.  (An  X05-02-000  moisture 

indicator can be used with 4A molecular sieve units to perform the 

same  function.)  On  units  with  metal  bowls,  a  moisture  indicator 

mounted on the cover performs the same color changing function. 

  2. The  4A  molecular  sieve  does  not  change  color.  For  moisture 

indication an X05-02-000 is recommended. See page 4.

  3. Environment  friendly  disiccant  changes  color  from  yellow/orange 

(meaning dry) to dark green (meaning wet).

  3. By installing two or more units in parallel, higher dry airflows  can be 

achieved.

Maintenance

  1.  The only servicing required for silica gel units is when the desiccant 

color or moisture indicator has changed from Blue (meaning dry) to 

Pink (meaning wet).  Should this color change occur:

 

 a.

 

Turn off and depressurize the line containing the dryer unit.

   b. Loosen the clamp ring and remove the bowl from the top housing.  

  (Figure 1) Proceed to step 2 or 3, as required.

  2. 

Desiccant replacement:

   a. Pour out used desiccant.
   b. Open new container and refill bowl. (Figure 2)
   c.   Shake  or  tap  bowl  to  settle  desiccant.  Add  or  remove  sufficient 

  quantity  to  fill  Model  X03  and  X25  unit  bowl  to  1/8"  below  inner  

  step, and for Model X06 fill bowl to within 1/2" of the top. (Figure 3)

!

 

    WARNING

FAILURE  OR  IMPROPER  SELECTION  OR  IMPROPER  USE  OF  THE 

PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS 

CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.

This  document  and  other  information  from  The  Company,  its  subsidiaries 

and authorized distributors provide product and/or system options for further 

investigation by users having technical expertise. It is important that you analyze 

all aspects of your application, including consequences of any failure and review 

the information concerning the product or systems in the current product catalog. 

Due to the variety of operating conditions and applications for these products 

or systems, the user, through its own analysis and testing, is solely responsible 

for making the final selection of the products and systems and assuring that all 

performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, 

specifications, designs, availability and pricing, are subject to change by The 

Company and its subsidiaries at any time without notice.

EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION 

IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. 

CONTACT YOUR LOCAL REPRESENTATIVE.

!

 

   

CAUTION

Polycarbonate bowls, being transparent and tough, are ideal for use with Filters 

and Lubricators. They are suitable for use in normal industrial environments, but 

should not be located in areas where they could be subjected to direct sunlight, 

an  impact  blow,  nor  temperatures  outside  of  the  rated  range.  As  with  most 

plastics, some chemicals can cause damage. Polycarbonate bowls should not 

be exposed to chlorinated hydrocarbons, ketones, esters and certain alcohols. 

They should not be used in air systems where compressors are lubricated with 

fire-resistant fluids such as phosphate ester and di-ester types.
Metal bowls are recommended where ambient and/or media conditions are 

not compatible with polycarbonate bowls. Metal bowls resist the action of most 

such solvents, but should not be used where strong acids or bases are present 

or in salt laden atmospheres. Consult the factory for specific recommendations 

where these conditions exist.

TO  CLEAN  POLYCARBONATE  BOWLS  USE  MILD  SOAP  AND WATER 

ONLY!  DO  NOT

  use  cleansing  agents  such  as  acetone,  benzene,  carbon 

tetrachloride, gasoline, toluene, etc., which are damaging to this plastic.

Bowl guards are recommended for added protection of polycarbonate bowls where 

chemical attack may occur.

Summary of Contents for STANDPIPE-PAC SSS-101

Page 1: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Page 2: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 3: ...mining Proper STANDPIPE PAC To Use 5 2 4 Example 1 6 2 5 Example 2 7 2 6 Options 8 2 6 1 Additional Audible Signals 8 2 6 2 Off Site Signaling Via Dialer 8 3 INSTALLATION 3 1 Unpacking 9 3 2 Location...

Page 4: ...32 4 4 5 To Refill Standpipe With Air Pressure After Fire Department Use 33 4 4 6 To Test Standpipe with Water Pressure 34 5 MAINTENANCE 36 5 1 Weekly 37 5 2 Monthly 37 5 3 Quarterly 38 APPENDICES App...

Page 5: ...formation is provided for the safety of installers operators and users of the UNITED Fire Systems STANDPIPE PAC equipment Carefully read understand and follow instructions identified by these symbols...

Page 6: ...ate at the time of publication but the data is published and presented without any guarantee or warranty whatsoever UNITED Fire Systems disclaims any liability for any use that may be made of the data...

Page 7: ...STANDPIPE PAC without instructions from UNITED Fire Systems the STANDPIPE PAC is not covered If you break tamper seals applied by UNITED Fire Systems the sealed parts are not covered Any problem that...

Page 8: ...air dryer dries the compressed air before entry into the standpipe as required by Boston FD TCM3 51725 3 Low limit pressure sensing switch This switch senses when the pressure in the standpipe drops b...

Page 9: ...side the location of the STANDPIPE PAC and wire the device in accordance with the instructions in this manual 17 An auxiliary condensate drain device This device permits manual draining of water in th...

Page 10: ...2 00 P N 10 540101 001 Page 3 INSTRUCTION NAMEPLATE 15 MANUAL AIR RELEASE BLEED VALVE CAP AND CHAIN Figure 2 Manual Air Release Bleed Valve Figure 4 Auxiliary Condensate Drain Device 17 AUXILIARY COND...

Page 11: ...determined by multiplying the length of each pipe by size by the internal volume per foot in gallons Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 1 1 2 X 0 106 2 X 0 174 2 1 2 X 0 2...

Page 12: ...the desired fill time at the bottom of the graph 2 3 2 Find the standpipe internal volume at the left of the graph 2 3 3 Determine the intersection of the lines from these two values 2 3 4 Choose the...

Page 13: ...101 001 Page 6 2 4 Example 1 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 6 750 X 1 500 1125 TOTAL 1125 gallons Required work can be performed in 1 2 hour 30 minutes so a fill time o...

Page 14: ...e 2 Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 2 80 X 0 174 14 6 100 X 1 500 150 8 550 X 2 600 1430 TOTAL 1594 gallons Fill time of 1 hour 60 minutes required Figure 7 Design Examp...

Page 15: ...his manual for further information See Paragraph 3 3 5 5 for installation instructions 2 6 2 Off Site Signaling Via Dialer The STANDPIPE PAC control unit is equipped with a built in dialer for off sit...

Page 16: ...3 2 1 Temperature Ensure that the STANDPIPE PAC unit is installed in a location that will not drop below 32 F 0 C at any time This may be accomplished by Choosing a location that will be supplied wit...

Page 17: ...t least 3 feet of clearance for personnel to access equipment for maintenance 3 3 Installation 3 3 1 Mounting See Figure 8 Mount the STANDPIPE PAC in the chosen mounting location It is strongly recomm...

Page 18: ...regular basis permitting any water accumulation or pooled water from testing to drain Dry standpipes installed with supervisory systems shall be installed per Figure 9 above The diagram indicates sev...

Page 19: ...and discard plastic plug from device inlet Valve 1 3 See Figure 10 Attach a inch close pipe nipple and the bull of a inch pipe tee to device inlet Valve 1 4 Install a convenient length of inch thread...

Page 20: ...1 60 3 4 10 6 0 7 11 3 3 3 5 3 Power Wiring See Table 3 Choose minimum conductor sizes and overcurrent protective device based on total current shown in table Connect power in junction box provided fo...

Page 21: ...NDPIPE PAC MODEL SSS 101 DESIGN INSTALLATION OPERATION AND MAINTENANCE MANUAL REVISION 2 00 P N 10 540101 001 Page 14 3 3 5 4 Battery Wiring See Figure 11 DO NOT connect battery until commissioning Fi...

Page 22: ...5 5 4 Optional Signaling Devices If additional audible devices are desired connect these devices to the notification appliance circuit serving the signal horn on the STANDPIPE PAC unit See Appendix D...

Page 23: ...9 optional signal horns Maximum Current Draw FOR ALL external Signal Horns INCLUDING required external audible visual device NOT including factory installed signal horn 1 0 A Maximum Length Of Notific...

Page 24: ...rn assembly on STANDPIPE PAC En End of Line Resistor 3 See Figure 13 2 Visually inspect Signal Horn base plate connections Locate positive and negative terminals on base plate NOTE RED wire connects t...

Page 25: ...all raceway from factory installed Signal Horn back box to additional Signal Horn NOTE See Table 4 for distance limitations 8 See Figure 13 6 Run 14 AWG Solid wires from additional Signal Horn through...

Page 26: ...Connect wires at additional Signal Horns IMPORTANT Do not branch Signal Horn circuit Run circuit from the first Signal Horn to the second Signal Horn then the second Signal Horn to the third and so on...

Page 27: ...ent capacity of the circuit when adding additional horns to the STANDPIPE PAC Each additional horn adjusted to FULL VOLUME draws 0 047 amps As noted on page 1 the current for all external devices incl...

Page 28: ...and 18 PSIG should be adequate for supervising the standpipe and providing prompt signaling if a valve is opened or a portion of the standpipe is removed Setting the HIGH pressure signal at 23 PSIG 2...

Page 29: ...ON 10 Press RESET button on control unit AC POWER indicator should be ON 11 ALARM indicator should be ON Signal horn should be sounding 12 Press SILENCE switch to acknowledge alarm Press SILENCE switc...

Page 30: ...lear and ALARM indicator should be OFF 12 When pressure gauge needle reaches approximately 18 PSIG compressor should automatically shut off HIGH LIMIT PRESSURE SENSING SWITCH TEST 13 Verify that compr...

Page 31: ...115 VAC not properly connected in junction box Properly connect power in junction box 3 3 5 3 STANDPIPE PAC does not build sufficient pressure in standpipe less than 7 PSIG One or more outlet valves o...

Page 32: ...nstalled in area where temperature cannot go below 32 degrees F Color of beads in air dryer has changed Air dryer beads have absorbed water to their capacity Compare color of beads to decal on side of...

Page 33: ...unit outlet lockable shutoff valve OPEN Has the battery been connected to the control unit Has 115 VAC power been turned ON Has the control unit RESET button been operated and is the control unit AC P...

Page 34: ...device been operated and is the pressure gauge needle moving UP When the pressure gauge needle reaches approximately 23 PSIG does the control unit ALARM indicator come ON and do the signals operate Ha...

Page 35: ...toff valve Is the control unit door locked Have the control unit keys lockable shutoff valve key s and UFS Manual P N 10 540101 001 been given to the responsible individual at the job site If the cont...

Page 36: ...s a yellow LED visible with unit door closed or open indicating trouble with the backup battery 4 1 3 5 Visual Indicator SYSTEM TRBL This is a yellow LED visible with unit door closed or open indicati...

Page 37: ...ON INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge Indicating between 13 and 18 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE Off Visual Indicator COMM FAIL Off Visual Ind...

Page 38: ...ignal Operation High Pressure In Standpipe If pressure increases in standpipe above 25 PSIG the following will be indicated HIGH PRESSURE IN STANDPIPE INDICATOR or CONTROL ITEM STATUS Visual Indicator...

Page 39: ...sor Disconnect Switch ON Control Test Service Device Not Operated 4 4 2 To Silence Piezo Sounder Press ACKNOWLEDGE SILENCE HOLD 2 SEC pushbutton once 4 4 3 To Silence Signal Horns Press ACKNOWLEDGE SI...

Page 40: ...ating less than 7 PSIG Visual Indicator AC POWER ON Visual Indicator ACTIVE ON Visual Indicator COMM FAIL Off Visual Indicator BATT FAULT Off Visual Indicator SYSTEM TRBL Off Visual Indicator SUPERVIS...

Page 41: ...points or traps without drains CLOSE Lockable Shutoff Valve BEFORE testing standpipe with water pressure Perform pressure test Use main drain and all drainage valves at low points to drain all water f...

Page 42: ...ry Condensate Drain Device to drain all water from piping in the vicinity of the STANDPIPE PAC It may take time for water to migrate from upper floors Allow sufficient time with drains open for all wa...

Page 43: ...PAC pressure gauge are APPROXIMATE Variation from nominal values can be expected IMPORTANT The STANDPIPE PAC unit including control unit has been pre wired and programmed at the factory for proper ope...

Page 44: ...in intact and connected to valve Valve OPEN Cap Disconnected or Missing If valve is OPEN CLOSE valve tightly If cap is disconnected re connect If cap is missing contact service provider for replacemen...

Page 45: ...For this reason it is recommended that the dryer desiccant be replaced quarterly NOTE Refer to Figure 15 1 Have Qty 1 UFS P N 21 100000 100 Replacement Desiccant available 2 Notify local personnel tha...

Page 46: ...se Qty 1 UFS P N 21 100000 100 13 Carefully align and insert desiccant bowl back into assembly until it is flush against air dryer cap 14 Depress tab marked PUSH and turn connecting ring until connect...

Page 47: ...compressor disconnect switch to OFF 3 Use 5 32 hex key to remove 2 hex screws holding black filter housing in place 4 Remove filter housing 5 Remove and discard existing foam filter element 6 Replace...

Page 48: ...ew filter 7 Monthly Has the Auxiliary Condensate Drain Device been properly used to remove water from the piping in the vicinity of the STANDPIPE PAC 8 Quarterly Has the HIGH PRESSURE signal been chec...

Page 49: ...LL CORRECTIONS REPAIRS MADE LIST ALL CORRECTIONS REPAIRS NEEDED NOTES PRINT NAME SIGNATURE DATE INSPECTOR CUSTOMER INSPECTION MAINTENANCE CHECKLIST STANDPIPE PAC SUPERVISORY SYSTEM UFS 236 REVISION 2...

Page 50: ...N 1 Remove Cover Cover is held on by two tamper resistant screws Removal key is en closed with pressure switch 2 Mounting the Switch The device is designed to be mounted in the upright or horizontal p...

Page 51: ...D770 08 00 2 I56 0551 009R System Sensor 2014 System Sensor warrants its enclosed pressure switch to be free from defects in materials and workmanship under normal use and service for a period of thr...

Page 52: ...to be mounted in the upright position side mounting is also acceptable Locate it where vibration shock and mechanical loading are minimal Refer to piping diagram above Fig 2 and 3 a Mount the device...

Page 53: ...W TRIP POINT SW1 SW2 MODELS EPS40 2 EPS120 2 SWITCHES AT HIGH TRIP POINT SW1 SW2 B COM A B COM A B COM A A COM B A COM B A COM B DUAL SWITCH MODEL EPS40 2 AND EPS120 2 1 Install pressure switch as sta...

Page 54: ...tion Perform pre ventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bimonthly Install a back up control for all critical applications where control...

Page 55: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 56: ...d the life of the coalescing element Specifications X06 X03 Plastic Bowl X03 Metal Bowl X04 X25 Metal Bowl Maximum Pressure 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150 psig 10 3 bar 150...

Page 57: ...ge meaning dry to dark green meaning wet 3 By installing two or more units in parallel higher dry airflows can be achieved Maintenance 1 The only servicing required for silica gel units is when the de...

Page 58: ...95 623 1 8 Clamp Ring GRP 96 404 1 GRP 96 404 1 NNR Not normally replaced The moisture indicator contains a weep orifice to provide an air sample to the moisture indicating paper Air leakage from thi...

Page 59: ...rated plastic bowl with a bowl or a new plastic bowl and bowl guard CAUTION Except as otherwise specified by the manufacturer this product is specifically designed for compressed air service and use w...

Page 60: ...ould be settled directly with the freight company WARNING Do not operate this compressor if damaged during shipment handling or use Damage may result in bursting and cause injury or property damage Lo...

Page 61: ...ed electrician wire the compressor to ensure that the supply line has the same characteristics voltage frequency and phasing as the motor Wiring must comply with all local and national codes CAUTION I...

Page 62: ...RCE THEN RELEASE ALL PRESSURE FROM THE SYSTEM BEFORE ATTEMPTING TO INSTALL SERVICE RELOCATE OR PERFORM ANY SERVICE The following instructions are based on NORMAL operation If the compressor is in an e...

Page 63: ...voltage to start motor Increase wire size if necessary to lower voltage drop 2 Consult factory adjust or replace 3 Be sure fuses and heaters are rated properly 4 Add receiver vessel or increase pipe...

Page 64: ...NGLE PHASE WIRING INSTRUCTIONS OIL LESS COMPRESSOR NOTE MOST MOTORS ARE MULTIPLE VOLTAGE CHECK NAMEPLATE AND VERIFY CORRECT INTERNAL CONNECTIONS FOR VOLTAGE BEING SUPPLIED TO UNIT FEEDER WIRE SIZE MUS...

Page 65: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 66: ...THIS SURFACE DELIBERATELY LEFT BLANK...

Page 67: ..._____________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth NJ USA 07033...

Reviews: