CIB UNIGAS - M039177CA
23
Combustion head pressure curves depending on the gas flow rate
Curves are referred to pressure= 0mbar in the combustion head!
The curves referred to the gas pressure in the combustion head, depending on the gas flow rate, are referred to the burner in the com-
bustion stage (3% of O
2
). During this stage, the combustion head, the gas butterfly valve and the servocontrol are at the maximum ope-
ning. Refer to Fig. 30, showing the correct way to measure the gas pressure, considering the values of pressure in combustion
chamber, surveyed by means of the pressure gauge or taken from the boiler’s Technical specifications.
Fig. 30
Key
1
Boiler
2
Gas pressure outlet on the boiler
3
Gas pressure outlet on the butterfly valve
4
Differential pressure gauge
Measuring the gas pressure in the combustion head
In order to measure the pressure in the combustion head, insert the pressure gauge probes: one into the boiler’s pressure outlet (Fig.
30-2) to get the pressure in the combustion chamber and the other one into the butterfly valve’s pressure outlet of the burner (Fig. 30-
3). On the basis of the measured differential pressure, it is possible to get the maximum flow rate: in the pressure - rate curves (showed
on the next paragraph), it is easy to find out the burner’s output in Stm3/h (quoted on the x axis) from the pressure measured in the
combustion head (quoted on the y axis). The data obtained must be considered when adjusting the gas flow rate.
NOTE: THE PRESSURE-RATE CURVES ARE GIVEN AS INFORMATION ONLY; FOR A PROPER SETTING OF THE GAS RATE,
PLEASE REFER TO THE GAS METER READING.
1
2
4
3
Summary of Contents for TP512A
Page 43: ...CIB UNIGAS M039177CA 43 Wiring diagram 21 001 2 Progressive burners ...
Page 44: ...CIB UNIGAS M039177CA 44 Wiring diagram 21 001 2 Fully modulating burners ...
Page 46: ...CIB UNIGAS M039177CA 46 ...
Page 47: ...CIB UNIGAS M039177CA 47 ...
Page 48: ...CIB UNIGAS M039177CA 48 ...
Page 49: ...CIB UNIGAS M039177CA 49 WIRING DIAGRAM Cod 09 315 1 Burners type TP525A Mod M MD x xx x 1 xx ...
Page 50: ...CIB UNIGAS M039177CA 50 ...
Page 51: ...CIB UNIGAS M039177CA 51 ...
Page 52: ...CIB UNIGAS M039177CA 52 ...
Page 55: ...CIB UNIGAS M039177CA 55 ...
Page 56: ......