For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
56
23
Master/Follower: Pulse Output
Introduction
The G3 can be configured in a master/follower scenario in many different ways. For information
concerning the G3’s RS485 master/follower function, see Application Guideline 9. The G3 has a high
frequency pulsed output as standard that can be used in conjunction with a Extended Terminal Block
Option Board (part number INV3-COM-D), to provide master/follower control. The pulse scenario
therefore requires one less option board than its RS485 counterpart. The INV3-COM-B can also be used
(see price book for more information on G3 option boards).
Connections
On the followers, connect the ribbon cable from the INV3-COM-D board to the drive’s CN6X connector. The CN6X connector is to
the left of the terminal strip.
Follower
Follower
Master
FP
CC
INV3-COM-D
INV3-COM-D
CC
PGB
CC
PGB
G3
G3
G3
to other followers
Programming for the Master
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Feedback Control Parameters
1
TERMINAL SELECTION PARAMETERS
“FP” Output Terminal Pulse Frequency
2
Programming for the Follower(s)
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Feedback Control Parameters
1
UTILITY PARAMETERS
Frequency Setting Parameters
1
FEEDBACK CONTROL PARAMETERS
PG Input: Number of Phases
1
FEEDBACK CONTROL PARAMETERS
Number of Pulses
360
FREQUENCY SETTING PARAMETERS
Frequency Priority Selection #1
4