*
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
61
Additional Programming
KEYSTROKE
RESULTING DISPLAY
LOCAL/REMOTE OUTPUT
FREQUENCY
0.0 Hz
READ/WRITE OUTPUT
FREQUENCY
0.0 Hz
READ/WRITE
hold down
OUTPUT
FREQUENCY
0.0 Hz
LOCAL/REMOTE
GROUP: SUPERUSER
READ/WRITE
RAMF
down arrow
RAM
down arrow
EEP
READ/WRITE 0380
up arrow until
04B9
READ/WRITE
something
arrows until
new value
(3)
READ/WRITE 04B9
alternating with
new value,
then
04B9
PRG OUTPUT
FREQUENCY
0.0 Hz
(3)
Example of how to determine the “new value”
Suppose “64” was the value found here. Converted to BCD, this is 0110 0100 (0110 binary is 6
decimal, 0100 binary is 4
decimal). Dancer control is turned on by setting the leftmost bit to ‘1’, so the
new BCD values will be
1
110 0100, which is
E4 in hex. Use the up arrow to adjust the 64 to read
E4.
Decimal
Binary
Hex
Digit
Decimal
Binary
Hex
Digit
Decimal
Binary
Hex
Digit
1 0001 1
6 0110 6 11 1011 B
2 0010 2
7 0111 7 12 1100 C
3 0011 3
8 1000 8 13 1101 D
4 0100 4
9 1001 9 14 1110 E
5 0101 5 10 1010 A 15 1111 F
Remove and re-apply main power to the drive after the above programming is finished.
In a normal PID scenario, the error signal the PID acts upon is the setpoint command minus the feedback;
with the above programming, the dancer PID acts upon the feedback (RX) only and tries to maintain it at
the zero setting. Therefore, any speed reference (from the RR or IV terminals, for example) has no effect
on drive output frequency when PID is on. NOTE, HOWEVER, THAT PID WILL NOT BE ACTIVE IF
THE SPEED REFERENCE IS ZERO (make sure the RR or IV terminals or other frequency reference
source are commanding at least 0.01 Hz. The actual value does not matter).