For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
57
If you want to stop/start the slave from the keypad, set Frequency Mode Selection in UTILITY
PARAMETERS to ‘1’ (remote input valid). This will allow the drive to follow an external frequency
reference even with the LOCAL/REMOTE LED illuminated.
The follower’s pulse input can be bias/gained to set up a ratio between drives. To make the follower run
half the speed of the master, program the following
into the follower
:
Group
Parameter
Value
FUNDAMENTAL PARAMETERS
Maximum Output Frequency
60
FREQUENCY SETTING PARAMETERS
PG Terminal Standard or Adjustable
1
FREQUENCY SETTING PARAMETERS
PG Reference Setting Point #1
0
FREQUENCY SETTING PARAMETERS
PG Ref Point #1 Frequency
0
FREQUENCY SETTING PARAMETERS
PG Reference Setting Point #2
100*
FREQUENCY SETTING PARAMETERS
PG Ref Point #2 Frequency
30
* The Bias/Gain of the PG input is dependent on the drive’s Maximum Output Frequency (MOF). In the
above example, if the MOF is left at 80 Hz, the follower will run at 22.5 Hz when the master is at 60 Hz
(the drive assumes MOF to be 100%).
Because the permissible adjustment range of the above parameters includes positive and negative values, a
follower direction change based on reference is possible.
12V
CC
FP
G3
CC
48,96, or 360 of these per output Hz per
second, as set by “FP” Output Terminal
Pulse Frequency in TERMINAL
SELECTION PARAMETERS group.