For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
22
(1)
see Guideline 6, Preset Speeds
(2)
see Guideline 5, Pattern Run
(3)
see Guideline 4, Binary Input
(4)
see Guideline 7, Motor Operated Pot
(5)
see Guideline 8, Three Line Control
(8)
see Guideline 16, Inverter/Bypass Switching
(6)
program DC Injection Start Frequency, DC Injection Current Magnitude, and DC Injection Time in the
PROTECTION PARAMETERS group. This function works only in remote mode. Also controls DC
inject at 0.0 Hz.
(7)
program Jog Run Frequency and Jog Stop Method in FREQUENCY SETTING PARAMETERS group.
(9)
could close with HOA switch in HAND position for G2/G2+ retrofit
(10)
could close with HOA switch in AUTO position for G2/G2+ retrofit.
(11)
When ESTOP is cleared, the drive will restart if frequency reference, direction, and enable are still
made; you may want to interlock one of these with your ESTOP circuit.
Programming example
Group
Parameter
New Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Terminal Selection Params Blind
1
TERMINAL SELECTION PARAMETERS
Input Terminal Selection
1
TERMINAL SELECTION PARAMETERS
“F” Input Terminal Function
43
TERMINAL SELECTION PARAMETERS
Potential Terminal Function
7
The above example programs the following:
The “F” terminal, when shorted to “CC”, acts like the LOCAL/REMOTE key on the keypad (notice
keypad LED) .The Potential Terminal, which does not physically exist, is assigned the function of
Enable. Whatever function is assigned to the Potential Terminal is always “on”. Therefore, the
jumper between ST-CC is now unnecessary. As a further example, if a value of 10 was placed
in Potential Terminal Function, the drive would do nothing but ESTOP.
The G3’s terminals can be programmed to activate their assigned functions
when a normally closed
contact opens
- contact factory for information on this Super User feature. See Guideline 10, Three Line
Control for a programming example
.