Acc/Dec Time Switching Frequency
Introduction
The G2 allowed a user to remotely select which of its two accel/decel times was active at any time via a
contact closure (from a prox switch for example) on its terminal strip. In addition to this, the G3 can
switch accel/decel times at a programmed output frequency. After the following programming is
completed, the drive will take about 10 seconds to ramp from 0 to 29.3 Hertz and about 1 second to ramp
from 29.3 to 60 Hertz.
Programming
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Fundamental Parameters #2 Blind
1
FUNDAMENTAL PARAMETERS #2
Acceleration Time #2
2.7
FUNDAMENTAL PARAMETERS #2
Deceleration Time #2
2.7
FUNDAMENTAL PARAMETERS #2
ACC/DEC #1/#2 Switch Frequency
29.3
FUNDAMENTAL PARAMETERS #1
Acceleration Time #1
27
FUNDAMENTAL PARAMETERS #1
Deceleration Time #1
27
In panel mode, give the drive a frequency command of 60 Hz and hit RUN. The decel times switch at 29.3
Hz when STOP is pressed.