For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
43
*** adjust this parameter until meter reads 566 VDC for a 460 volt drive or 283 VDC for a 230 volt drive
(from chart on page 2). Hit ENTER when adjusted.
Example of on-the-fly calibration of the AM terminal for output voltage
¾
Adjust jumper 4 for 0-1 or 4-20 mA output
¾
Connect meter to ‘AM’ and ‘CC’
.
¾
Run the drive at some high frequency, say 60 Hertz.
¾
Programming
Group
Parameter
New Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
AM/FM Adjustment Parameters Unblind
1
AM/FM TERMINAL ADJUSTMENT PARAMETERS
AM Terminal Function Selection
5
AM/FM TERMINAL ADJUSTMENT PARAMETERS
Frequency Meter Adjustment
****
**** use the up/down arrows to make meter read the same value as the drive is displaying here. Hit ENTER when adjusted.