For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
13
If Preset Speed Mode Activation is changed to “1”, then the direction, ACC/DEC time, and V/Hz pattern
associated with that preset speed is determined solely by the Preset Speed #
n
Operating Mode
(FREQUENCY SETTING PARAMETERS group) as seen in the manual. A F-CC or R-CC closure must
still be made to run preset speeds, but the direction the closure represents is ignored.
TIP: If you have from two to four preset speeds, use speeds #1, 3, 7, and 15. This reduces the number of
contact openings/closings that have to take place.