1
Programmable Monitoring
The G3 has an extensive monitoring system which is employed via the keypad. The information
given in the monitor displays is useful while troubleshooting or commissioning applications.
Key
Display
Description
MOTOR RUN DIRECTION:
FORWARD
Indicates direction associated with speed reference. Keypad direction reference
is separate from terminal strip direction reference.
MONITOR #1
MONITOR #2
PROGRAMMABLE
MONITOR #3
SEE BELOW
MONITOR #4
STATUS: R:-- S1:-- S2:--
S3:-- S4:-- S5:--
As these
input
terminals are shorted to CC, the “--” will change to “ON”. Use
this as a troubleshooting tool.
ST:ON F:-- RES:--
S6:-- S7:-- S8:--
As these
input
terminals are shorted to CC, the “--” will change to “ON”. Use
this as a troubleshooting tool. S6, S7, and S8 exist only on option card.
RCH:-- LOW:-- FLT:--
OUT:-- FAN:-- MC:ON
As these
output
terminals close, the “--” will change to “ON”. Use this as a
troubleshooting tool. OUT exists only on option card. MC always says “ON”.
“FAN” shows “ON” when the drive’s muffin fan is on.
CUMULATIVE RUN TIME
0.00
.01 represents one hour. The timer is not resettable. An output contact can be
programmed to change state based on the CRT.
PAST TRIP #1
NO ERROR
PAST TRIP #2
NO ERROR
The drive stores past faults; to clear these, put a “4” into Standard Setting Mode
Selection in the UTILITY PARAMETERS group.
PAST TRIP #3
NO ERROR
PAST TRIP #4
NO ERROR
MOTOR RUN DIRECTION:
FORWARD
End/beginning of MONITOR mode
*
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
4