ETS communication objects
Manual DALI gateway S64 KNX/S128 KNX
36
Sends the set Y value as status of the group.
8.5
ECG objects
8.5.1
ECG objects – behaviour
A communication object is available for each of the up to 64 connected ECGs and corresponding
lamps to display the failure status. (Example ECG 1):
Object Object name
Function
Type
Flags
519
ECG1, Switching
On/Off
1 Bit
1.001
CW
Use this object to switch an ECG on or off if it is not in special mode (test mode, emergency
lights, panic/ emergency mode).
520
ECG1, Dimming
Brighter/Dar
ker
4 Bit
3.007
CW
This object is used for the relative dimming of an ECG that is not in special mode (test mode,
emergency lights, panic/ emergency mode). Bit 3 is set to dim up and deleted to dim down.
Bits 0 to 2 refer to the increment size. Bit 0 to 2 deleted is interpreted as a stop telegram.
521
ECG 1, Set Value
Value
1 Byte
5.001
CW
Sets the value of ECG1 unless it is in special mode (test mode, emergency lights, panic/
emergency mode).
522
ECG1, Enable
Yes/No
1 Bit
1.003
CW
Note:
Object 522 is shown for the following parameter: ECG 1
General
Function of the
additional object.
Use this object to enable the operation of ECG 1:
Object = 0
Operation disabled Object = 1
Enable operation
522a ECG1, Disable
Yes/No
1 Bit
1.003
CW
Use this object to disable the operation of ECG 1:
Object = 0
Enable operation Object = 1
Operation disabled
523
ECG1, Status
On/Off
1 Bit
1.001
CRT
Sends the ECG switch status. Each value >0% is interpreted as ON.
524
ECG 1, Status
Value
1 Byte
5.001
CRT
Sends the ECG value status.