Manual Mode
Manual DALI gateway S64 KNX/S128 KNX
17
all lights via broadcast. The LED on button 1/9 shows the switch status. All lights react to a
broadcast command even if group assignment has not yet taken place.
A long keypress on button 5/13 triggers a quick exchange command. This function makes it
possible to replace a faulty ECG even without the ETS (see chapter 11.5 ECG easy replacement.
A long keypress on button 6/14 activates the converter inhibit mode. If the power supply for the
connected emergency lights is turned off within 15 minutes after activating the converter inhibit
mode, the lights are turned off instead of changing into emergency mode. This operating mode
may be necessary during the commissioning and installation process to prevent constant
emergency lighting and battery discharge.
If the gateway detects a fault, the LEDs on buttons 2/10 to 4/12 and 7/15 to 8/16 show the
exact type of fault. The LED is constantly lit up in red. The faults are as follows:
LED Button 2/10
Converter fault
LED Button 3/11
ECG fault
LED Button 4/12
Lamp fault
LED Button 7/15
DALI short-circuit
LED Button 8/16
KNX fault