ETS communication objects
Manual DALI gateway S64 KNX/S128 KNX
29
80a
G1, Failure Exceeds
Threshold
Yes/No
1 Bit
1.005
CRT
This object is used to report that the total of all lamps, ECG and converter failures found within
the group exceeds the threshold set via parameters.
80b
G1, Failure Rate in Total
Value
1 Byte
5.010
CRT
The total number of light and ECG errors within the group is reported via this object.
80c
G1, Failure Rate in %
Value
1 Byte
5.001
CRT
This object is used to report the error rate as a percentage of the total number of devices
within the group.
Object 95-97 will be displayed on: G1
Analysis and Service
Operating Hour Calculation
95
G1, Operating Hours Reset
Yes/No
1 Bit
1.015
CW
The operating hours within the group can be reset with „1“ via this object.
96
G1, Operating Hours
Value
4 Byte
13.100
CW
Counts the operating hours in the group. This value is transmitted in seconds according to DTP
13.100.
97
G1, Life Time Exceeded
Yes/No
1 Bit
1.005
CW
This object shows whether the maximum life span set in the parameters has been exceeded.
Note
: If the treshold has been exceeded, an alarm is issued via this object (by sending “1“).
This status is resent for each further hour that is above the threshold.
Objects for colour control
Different colour control options are supported:
•
Colour temperature
•
RGB
•
HSV
•
RGBW
•
XY
Only one type of colour control can be selected for a group. All ECGs in the group that support
this type can thereby be controlled. Other ECG types will not react to the command. Please
remember to only assemble ECGs with the same colour control in a group.
Colour temperature
Depending on the type of colour control, different objects are shown:
Figure 3: Colour temperature (Source: Wikipedia)