ETS communication objects
Manual DALI gateway S64 KNX/S128 KNX
34
See colour change red.
89
G1, Colour Fading White
Brighter/Cooler
4 Bit
3.007
CW
See colour change red.
91
G1, Colour (RGB) Red
Status
1 Byte
5.001
CRT
Sends the selected colour red as status of the group.
92
G1, Colour (RGB) Green
Status
1 Byte
5.001
CRT
Sends the selected colour green as status of the group.
93
G1, Colour (RGB) Blue
Status
1 Byte
5.001
CRT
Sends the selected colour blue as status of the group.
94
G1, Colour White
Status
1 Byte
5.001
CRT
Sends the selected colour white as status of the group.
HSVW (separate objects)
See chapter: HSV (page 33).
XY (DPT 242.600)
The colour is identified through an XY value between 0 and 1. This value range is converted into
a range from 0 to 65535 (2 Byte floating point) in the KNX. The value 65535 corresponds to
value 1 in the diagram.
Figure 7: XY-colour spectrum (Source: Wikipedia)