ETS parameters
Manual DALI gateway S64 KNX/S128 KNX
56
Parameter
Settings
ECG x, Description
e.g.: Floor, 1 level
With this parameter an ECG description can be defined. This description is displayed as an
overview for all communication objects. Example for the description: Floor, 1 level.
Group Assignment
Not assigned
Group 1
…
Group 16
The group assignment is configured via the DCA or via the website and is only displayed here.
ECG Type
Fluorescent Lamp
Self Contained Battery Lamp (non switchable)
Self Contained Battery Lamp (switchable)
Discharge Lamp
Low Voltage Lamp
Incandescent Lamp
0..10V Converter
LED Module
Relay Module
ECG with Colour Control
Use this parameter to set the type of ECG used.
Operating Mode
Normal Mode
Permanent Mode
Normal / Night Mode
This parameter allows to set the operating mode in which the ECG shall be operated. Night
operation is controlled via a central object no. 12.
Function of Additional Objectt
No Obejct
Disable Object
Release Object
This parameter can be used to define the function of an additional object. If the "Disable
object" is selected, an object is displayed which blocks operation of the ECG if the value is "1".
If the "Enable object" is selected, an object is displayed which enables operation of the ECG if
the value is "1".
Note:
Disable function only refers to ON/OFF and value setting commands via KNX objects
Behaviour on Enable
No Chance
Switch to ON-Value
Switch to OFF-Value
This parameter is displayed when an additional object is selected. The behaviour during
activation can be defined here..
Behaviour on Disable
No Chance
Switch to ON-Value
Switch to OFF-Value
This parameter is displayed when an additional object is selected. The behaviour during
deactivation can be defined here..
Value in Permanent Mode
1..100%
[50%]