Instruction manual

Siemens tiastar

 Gateway Unit

Summary of Contents for Tiastar LV MCC

Page 1: ...www usa siemens com Instruction manual Siemens tiastar Gateway Unit ...

Page 2: ...work nodes 14 3 2 STEP 2 Launch gateway configuration software 15 3 3 STEP 3 Review the network addressing 17 3 4 STEP 4 Connect to the Profibus configuration port 18 3 5 STEP 5 Download the Profibus configuration 19 3 6 STEP 6 Connect to gateway configuration port 20 3 7 STEP 7 Launch hyperterminal 21 3 8 STEP 8 Cycle power to the gateway 24 3 9 STEP 9 Configure the gateway 25 3 9 1 Choose Option...

Page 3: ...n This involves the following steps Connect to the gateway using HYPERTERMINAL and configuring operation Create the Profibus network configuration of the MCC Download Download the Profibus configuration to the gateway Verify Verify the proper operation of the gateway s Instruction manual tiastar Gateway Unit 1 Siemens Industry Inc 2011 All rights reserved ...

Page 4: ...s Instruction manual tiastar Gateway Unit 2 Siemens Industry Inc 2011 All rights reserved ...

Page 5: ...2 Configure Profibus Network for Gateway The program we will be using is s Instruction manual tiastar Gateway Unit 3 Siemens Industry Inc 2011 All rights reserved ...

Page 6: ...2 1 Step 1 Create a new project s Instruction manual tiastar Gateway Unit 4 Siemens Industry Inc 2011 All rights reserved ...

Page 7: ...2 2 Step 2 Add the Master Unit Select the Anybus Master object and drag it over to the network area s Instruction manual tiastar Gateway Unit 5 Siemens Industry Inc 2011 All rights reserved ...

Page 8: ... 3 Step 3 Configure the Master Double click to configure the master You will then get this default configuration s Instruction manual tiastar Gateway Unit 6 Siemens Industry Inc 2011 All rights reserved ...

Page 9: ...Select the MULTI MASTER DP configuration setting Then save it by pressing OK s Instruction manual tiastar Gateway Unit 7 Siemens Industry Inc 2011 All rights reserved ...

Page 10: ... available for Pro C Select the SIMOCODE object from the device tree and drag to the network line on the master This is what the simocode device looks like after being added to the network configuration Select the device type and drag it over to the slot configuration s Instruction manual tiastar Gateway Unit 8 Siemens Industry Inc 2011 All rights reserved ...

Page 11: ...is what the simocode device looks like after being added to the network configuration and having the slot configured s Instruction manual tiastar Gateway Unit 9 Siemens Industry Inc 2011 All rights reserved ...

Page 12: ...hardware configuration prior to reading this section The SIMOCODE shows additional steps that are deliberately not shown here for brevity Select the SIRIUS 3RW44 object from the device tree and drag to the network line on the master s Instruction manual tiastar Gateway Unit 10 Siemens Industry Inc 2011 All rights reserved ...

Page 13: ...Select the device type and drag it over to the slot configuration s Instruction manual tiastar Gateway Unit 11 Siemens Industry Inc 2011 All rights reserved ...

Page 14: ...ODE shows additional steps that are deliberately not shown here for brevity Important Note Always choose the PPO 1 version of the unit Select the MICROMASTER 4 object from the device tree and drag to the network line on the master Select the device type and drag it over to the slot configuration s Instruction manual tiastar Gateway Unit 12 Siemens Industry Inc 2011 All rights reserved ...

Page 15: ...he network configuration you must save the file 2 7 Step 7 Save file The final configuration of the network and device should look something like this s Instruction manual tiastar Gateway Unit 13 Siemens Industry Inc 2011 All rights reserved ...

Page 16: ...ng the gateway Download unit configuration files to each smart device that does not allow configuration via keypad Enter node addressing to each smart device via keypad that does not receive downloaded unit configuration files from above s Instruction manual tiastar Gateway Unit 14 Siemens Industry Inc 2011 All rights reserved ...

Page 17: ...3 2 Step 2 Launch Gateway Configuration Software The Program we will be using is s Instruction manual tiastar Gateway Unit 15 Siemens Industry Inc 2011 All rights reserved ...

Page 18: ...Open the xml gateway configuration file s Instruction manual tiastar Gateway Unit 16 Siemens Industry Inc 2011 All rights reserved ...

Page 19: ...3 3 Step 3 Review the Network Addressing Record these numbers for later use Input 24 23 1 Output 18 17 1 s Instruction manual tiastar Gateway Unit 17 Siemens Industry Inc 2011 All rights reserved ...

Page 20: ...ort On the Profibus Master side of the Anybus X Gateway connect your RS 232 DB9FF Null Modem Cable to the Master Config Port and the serial port on your computer s Instruction manual tiastar Gateway Unit 18 Siemens Industry Inc 2011 All rights reserved ...

Page 21: ...3 5 Step 5 Download the Profibus Configuration s Instruction manual tiastar Gateway Unit 19 Siemens Industry Inc 2011 All rights reserved ...

Page 22: ...the serial port on your computer 2 On the EtherNet IP or Modbus TCP IP side of the Anybus X Gateway connect your RS 232 DB9FF Null Modem Cable to the Gateway Config Port and the serial port on your computer 3 On the Modbus RTU side of the Anybus X Gateway connect your RS 232 DB9FF Null Modem Cable to the Gateway Config Port and the serial port on your computer s Instruction manual tiastar Gateway ...

Page 23: ...3 7 Step 7 Launch HyperTerminal The Program we will be using is s Instruction manual tiastar Gateway Unit 21 Siemens Industry Inc 2011 All rights reserved ...

Page 24: ...Select the COM port to connect with Dependant upon machine Press the CONFIGURE button to set up the communication parameters of the port to connect with the gateway s Instruction manual tiastar Gateway Unit 22 Siemens Industry Inc 2011 All rights reserved ...

Page 25: ...When the Hyper Terminal setup is complete this blank screen should appear s Instruction manual tiastar Gateway Unit 23 Siemens Industry Inc 2011 All rights reserved ...

Page 26: ...s screen promptly after cycling power to the gateway If you don t see this display recheck the cable step 6 or the communications settings step 7 and cycle power again s Instruction manual tiastar Gateway Unit 24 Siemens Industry Inc 2011 All rights reserved ...

Page 27: ...3 9 Step 9 Configure the Gateway You should see this screen Press ESC s Instruction manual tiastar Gateway Unit 25 Siemens Industry Inc 2011 All rights reserved ...

Page 28: ...3 9 1 Choose Option 4 Show fieldbus system configuration s Instruction manual tiastar Gateway Unit 26 Siemens Industry Inc 2011 All rights reserved ...

Page 29: ...nge configuration This is from the downloaded profibus configuration Refer to step 3 and verify the numbers match Press ESC to continue s Instruction manual tiastar Gateway Unit 27 Siemens Industry Inc 2011 All rights reserved ...

Page 30: ...Press Y s Instruction manual tiastar Gateway Unit 28 Siemens Industry Inc 2011 All rights reserved ...

Page 31: ...output byte sizes IMPORTANT Notice how the input output byte sizes are swapped from option 4 This is required for proper operation s Instruction manual tiastar Gateway Unit 29 Siemens Industry Inc 2011 All rights reserved ...

Page 32: ...Press Y s Instruction manual tiastar Gateway Unit 30 Siemens Industry Inc 2011 All rights reserved ...

Page 33: ...Press Y s Instruction manual tiastar Gateway Unit 31 Siemens Industry Inc 2011 All rights reserved ...

Page 34: ...ect the serial cable to profibus configuration port Refer to step 4 Press this button for online monitoring The color of the device border indicates the connection of the unit Green The unit is connected and communicating to the master Red The unit is not connected or communicating to the master s Instruction manual tiastar Gateway Unit 32 Siemens Industry Inc 2011 All rights reserved ...

Page 35: ...7 400015 28 29 401039 28 29 400016 30 31 401040 30 31 400017 32 33 401041 32 33 400018 34 35 401042 34 35 400019 36 37 401043 36 37 400020 38 39 401044 38 39 400021 40 41 401045 40 41 400022 42 43 401046 42 43 400023 44 45 401047 44 45 400024 46 47 401048 46 47 400025 48 49 401049 48 49 400026 50 51 401050 50 51 400027 52 53 401051 52 53 400028 54 55 401052 54 55 400029 56 57 401053 56 57 400030 5...

Page 36: ... 111 400057 112 113 401081 112 113 400058 114 115 401082 114 115 400059 116 117 401083 116 117 400060 118 119 401084 118 119 400061 120 121 401085 120 121 400062 122 123 401086 122 123 400063 124 125 401087 124 125 400064 126 127 401088 126 127 400065 128 129 401089 128 129 400066 130 131 401090 130 131 400067 132 133 401091 132 133 400068 134 135 401092 134 135 400069 136 137 401093 136 137 40007...

Page 37: ... 400100 198 199 401124 198 199 400101 200 201 401125 200 201 400102 202 203 401126 202 203 400103 204 205 401127 204 205 400104 206 207 401128 206 207 400105 208 209 401129 208 209 400106 210 211 401130 210 211 400107 212 213 401131 212 213 400108 214 215 401132 214 215 400109 216 217 401133 216 217 400110 218 219 401134 218 219 400111 220 221 401135 220 221 400112 222 223 401136 222 223 400113 22...

Page 38: ... 400144 286 287 401168 286 287 400145 288 289 401169 288 289 400146 290 291 401170 290 291 400147 292 293 401171 292 293 400148 294 295 401172 294 295 400149 296 297 401173 296 297 400150 298 299 401174 298 299 400151 300 301 401175 300 301 400152 302 303 401176 302 303 400153 304 305 401177 304 305 400154 306 307 401178 306 307 400155 308 309 401179 308 309 400156 310 311 401180 310 311 400157 31...

Page 39: ... 400188 374 375 401212 374 375 400189 376 377 401213 376 377 400190 378 379 401214 378 379 400191 380 381 401215 380 381 400192 382 383 401216 382 383 400193 384 385 401217 384 385 400194 386 387 401218 386 387 400195 388 389 401219 388 389 400196 390 391 401220 390 391 400197 392 393 401221 392 393 400198 394 395 401222 394 395 400199 396 397 401223 396 397 400200 398 399 401224 398 399 400201 40...

Page 40: ... 401255 460 461 400232 462 463 401256 462 463 400233 464 465 401257 464 465 400234 466 467 401258 466 467 400235 468 469 401259 468 469 400236 470 471 401260 470 471 400237 472 473 401261 472 473 400238 474 475 401262 474 475 400239 476 477 401263 476 477 400240 478 479 401264 478 479 400241 480 481 401265 480 481 400242 482 483 401266 482 483 400243 484 485 401267 484 485 400244 486 487 401268 48...

Page 41: ...5 Device Data 5 1 SIMOCODE s Instruction manual tiastar Gateway Unit 39 Siemens Industry Inc 2011 All rights reserved ...

Page 42: ...l data Information located in the Presetting column may vary dependant upon device configuration See the Simocode Pro System Manual for more detail s Instruction manual tiastar Gateway Unit 40 Siemens Industry Inc 2011 All rights reserved ...

Page 43: ...5 2 RVSS 3RW44 s Instruction manual tiastar Gateway Unit 41 Siemens Industry Inc 2011 All rights reserved ...

Page 44: ...s Instruction manual tiastar Gateway Unit 42 Siemens Industry Inc 2011 All rights reserved ...

Page 45: ...5 3 VFD MM440 s Instruction manual tiastar Gateway Unit 43 Siemens Industry Inc 2011 All rights reserved ...

Page 46: ...s Instruction manual tiastar Gateway Unit 44 Siemens Industry Inc 2011 All rights reserved ...

Page 47: ...trol word defined above STW1 2 3 Frequency reference to the VFD 0 6000 HSW Bytes In Meaning Chart Ref 0 1 Status word defined above ZSW 2 3 Speed feedback in HZ 0 6000 HIW The rest of the bytes 8 are used by the PLC program to transfer parameters and data between the drive and the PLC s Instruction manual tiastar Gateway Unit 45 Siemens Industry Inc 2011 All rights reserved ...

Page 48: ...ly general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract All product designations may be trademarks or product names of Siemens AG or supplier compan...